COMMERCE BUSINESS DAILY ISSUE OF AUGUST 21,2000 PSA#2668 U.S. Dept. of Commerce, NOAA, WASC, Acquisition Management Division
WC3, 7600 Sand Point Way NE, Seattle, WA 98115-6349 66 -- REQUEST FOR QUOTATIONS FOR ULTRAVIOLET DISINFECTION SYSTEM. SOL
WASC-0-1403 DUE 090100 POC Randall Brown (206) 526-6226/FAX (206)
526-6025 Request for quotations issued for the following products: 01)
ultraviolet disinfection systems for John Day salt water holding
facility. Each unit to be capable of providing a dosage of 90,000
micro-watt seconds per square center @ 254 nm, at a flow of 175 gpm,
based on 90% water transmission. Lamps shall be low pressure mercury
vapor with hard glass enclosure, having a guarantee of 9,000 hours to
end of life at 60% of original output. All wetted parts shall be 316L
stainless steel, welded using the plasma fusion arc method, polished
and passivated after fabrication. Heads shall be threaded for removal
for interior access. Exterior non-wetted surfaces shall be polished and
passivated after fabrication. Manufacturer's standard controls shall be
furnished and mounted in a NEMA 4X panel. Include independently fused
fan cooling system, light-out warning LED display, and elapsed hour
meter. Qty. 2 each. 02) Rotary drum filter. Unit shall consist of a
screened drum driven by an electric motor through a gear reducer,
revolving inside a fiberglass surround tank. The inlet water enters the
interior of the screen, and the discharge is on the exterior of the
screen. The unit shall be designed so that the sludge drops into a
discharge trough as the screen revolves. A spray system shall be
included to clean the screen at a minimum spray pressure of 80 psi,
with discharge into the trough. The unit shall be constructed of 316L
stainless steel, fiberglass, and suitable plastics, with the basin of
fiberglass, the drum frame of 316 stainless, and the screen panels of
plastic. Other parts constructed so as to hold the amount of stainless
in contact with the water stream to a minimum. The motor and gear
reducer shall be enclosed and exterior mounted. The minimum flow rate
is 25 pm TSS, using 60 micron shall be not less than 365 gpm.
Rotational speed 5 rpm. Maximum submergence of drum 60% (controlled by
exterior standpipe by others). The rotation and backwashing shall be
automatic, actuated by the increase of the head on the drum. The
controls to accomplish this shall be enclosed in a NEMA-X box (except
for a low voltage float control). Spare parts with the unit must
include a complete elastomeric drum seal, two screen panels, and twenty
screen patching plugs. Qty. 1 ea. 03) Sand filters, non-metallic. Must
be of non-corrosive construction (no metals in contact with water).
Filter body fiberglass and polyester resin with a working pressure of
50 psi. Stand, flanges, diffusers, and laterals of PVC and/or
polypropylene construction. Filter area must be not less than 26 sq.
ft. Tank diameter not to exceed six feet. Minimum capacity 1,600 pounds
of gravel and 6,000 pounds of silica sand. Four inch, 150 pound water
connection flanges. Must include dual gages with brackets and fittings
for tapes into inlet and outlet by owner. Fill lid, manual air relief
valve, water drain and sand drain plugs. MUST BE COMMERCIAL PRODUCTS
IN USE FOR AT LEAST FIVE YEARS, CUSTOM MADE PRODUCTS NOT ALLOWED.
Provide catalog cuts/brochures of proposed system.Provide Federal tax
ID number and DUNS number with quote. State if small-, minority-, or
women-owned business with quote. This is a simplified acquisition with
an estimated value of less than $100,000. Posted 08/17/00