COMMERCE BUSINESS DAILY ISSUE OF JULY 5,2000 PSA#2635U.S. Army CECOM, CECOM Acquisition Center, Fort Monmouth, NJ
07703-5008 61 -- MARKET SURVEY FOR 3KILOWATT(KW) ELECTRIC POWER GENERATION SYSTEM
POC Mr.Raymond Billings, 703-704-3200 This is a Market Survey seeking
sources which have the capability to provide the following: A 3
KILOWATT (kW) 0.8 POWER FACTOR (pf), 400-HERTZ (Hz) AND 60-Hz
ALTERNATING CURRENT (ac), DIESEL FUELED ELECTRIC POWER GENERATION
SYSTEMS. Contact Point, Raymong Billings at (703)704-3200. The U.S.
ARMY Communications Electronics Command (CECOM) requests information
from manufacturing sources regarding their capability to manufacture
the current DoD 3 kW Tactical Quiet Generator (TQG) using Government
furnished drawings or provide a mature commercial design meeting the
following requirements. Mobile Electric Power (MEP) 3 kW generator
requirements are to be met with a diesel fueled engine, generator, and
all normal operating controls and protective devices. The equipment
must provide full rated power over the full range of military ambient
operating conditions (+120o F to -25o F), including 1,000 feet and 107o
F. Output frequencies of these sets are 400-Hz and 60-Hz. Voltage and
phase connections for these sets are 120-volt single phase and
120/240-volt single phase. The audio noise sound pressure level (SPL)
for these sets are from 70 dB(A) at 7 meters from the set and 85 dB(A)
at 0.7 meter from any point on the control panel. The sets shall also
have a 24-volt starter system along with a 24-volt standard NATO slave
receptacle. The set weight is 326 pounds, including the battery and a
full tank of fuel, it shall also have a manual starting system. The
sets shall be storable at any possible humidity from +160o F to -60o F
and in a salt-fog environment. Include an onboard fuel tank capable of
supporting eight hours of continuous operation at rated load and also
have the capability of operating from external fuel sources. The set
shall be operable when sited in any direction on uneven terrain with
grades up to 15o. The engine exhaust shall exit the set in an upward
direction. The set shall provide automatic shutdown (with manual
override) due to over speed, low fuel, low oil pressure, high
temperature and over voltage. The sets shall survive the effects of
High Altitude Electromagnetic Pulse (HAEMP) and meet standard military
Electro-Magnetic Interference (EMI) requirements. The minimum
reliability of the set shall be 500 hours Mean Time Between Failures
(MTBF) at a 90% Lower Confidence Level (LCL). The sets must also be
marine, rail, highway and air transportable. The set dimensions shall
not exceed a length of 35 inches, a width of 28 inches, and a height of
27 inches. The Government will not pay for information submitted. All
proprietary and restricted information shall be clearly marked.
Estimated quantity is 15,400 each from calendar year 2002 through 2008
with a delivery rate of approximately 200 sets per month. Request that
specific product literature, technical information as well as
organization profile be supplied not later than 1 August 2000 to:
Project Manager-Mobile Electric POW, 10205 Burbeck Road, Suite 105,
Fort Belvoir, VA 22060-5863, ATTN: AMSEL-DSA-MEP-T, Mr. Raymond
Billings. Posted 06/30/00 (W-SN470875). (0182) Loren Data Corp. http://www.ld.com (SYN# 0274 20000705\61-0005.SOL)