COMMERCE BUSINESS DAILY ISSUE OF MAY 24,2000 PSA#2607Department of Veterans Affairs Medical Center, 500 West Fort St.,
Boise, ID 83702 44 -- BOILER FEED SYSTEM & TWO BOILERS SOL 531-34-00 DUE 060200 POC
Carol Grant Barr (208) 422-1131or fax (208) 422-1139 E-MAIL: click here
to contact the contracting officer via, carol.barr@med.va.gov. This is
a combined synopsis/solicitation for the purchase of commerical item.
This notice is prepared in accordance with the format in Subpart 12.6,
as supplemented with additional information included in this notice.
This announcement constitutes the only only solicitation and is issued
as a request for Proposal. The applicable Standard Industrial Code is
5074. A written solicitation will not be issued. This solicitation
document and incorperated clauses and provisions are those in effect
through Federal Acquisition Circular 97-03. The Statement of Work (SOW)
and incorporated clauses will govern any resulting contract awarded as
a result of this solicitation. This VA Medical Center requires: Boiler
Feed System:Therma-Feed Boiler Feed System Model T-100-270E-TH2A OR
EQUAL.Capacity:100HP 3,450 LBS/HR Total Load. Storage Tank:27" x 36"
receiver with epoxy lining & anode. 70 gallons to overflow. Pump
Capacity: 2 quantity 6GPM with 253 ft. TDH with 2HP 3,450RPM motor
Centrifugal Boiler feed pumps with mechanical seals: 270E. Heating
Capacity: Based on 100% makeup and a blend temperature of 150 degrees
F. 6.9gpm from 150 degrees to 205 egrees F. using 75 PSI. Make Up
Valve: Capacity at 40PSI: 17GPM Structural Stand Height: 48". Nema 1
control panel with control circuit transformer,HOA switches, run
lights, on off switch, and main disconnect. Pump motor starters with
integral circuit breakers. Electrical: 208/60/3 phase 2" insulation
with jacket and cast hard top walkway. 4.5" pressure gauge in lieu of
standard 3" BOILERS, Two each 50HP 150S TTTP Sellers Immersion Fired
Steam Boiler Natural Gas with a dedicated burner for each tube OR
EQUAL. 2,092 MBH, 3HP Blower motor, UL Approved 208/60/3 phase 1000BTU
Standard Gas Pressure with following features: 1)Boiler Shell W/ High
Efficiency Heat extractors and handhole assembly. 2)2" insulation with
hard "walk on" top and steel jacket.3)Welded structural steel base.
4)Operating pressure controls. 5)Hinge mount combustion assembly W/
blower unit and the following:A.Air proving switch; B. Burner nozzles
and runner pilots; C. Spark ignition and flame rod; D. Pilot and main
gas regulators. 6)High limit with manual reset. 7)Pressure gauge, 4 "
dial type. 8)Pop safety valve. 9)Dual float LWCO'S (secondary w/m
reset).10)Control Panel box NEMA 1 with the following components:A.
Program type combustion safeguard E110; B. Magnetic motor starting
switch;C. On off switch; D. Primary and secondary fuses;E. Control
circuit transformer, 55 VA; F. 7 indicating lights. 11)Safety Valve set
@ 75 psi. 12) Water column blowdown valves. 13) M.P. Control. 14) Must
fit through a max.. opening of 44" x 84" and be no longer than 8' 4".
Delivery date required of above items is July 31, 2000. Each proposal
will be accompanied by manufacturer's data supporting compliance with
above requirements. Proposal shall include all delivery charges. The
following factors shall be used for evaluations: (1) Technical
capability of the item offered to meet the minimum requirements listed
above, (2) Warranties, (3) Delivery Schedule, ability to meet the
7/31/00 date and (4) price factor is of equal importance to (1), (2)
and (3). All responsible bidders may submit a written offer for
consideration by the Government. A firm fixed priced contract resulting
from this solicitation will be awarded to the responsible offereor
whose offer conforming to this solicitation is most advantagious to the
Government. Federal Acquisition Regulation (FAR) provisions at 52.212-1
and 52.212-3 apply to receipt of offers and are herby incorperated by
reference. FAR clause 52.249-8, Default is added as addenda and are
hereby incorporated by reference. Offeror's are reminded to include a
comleted copy of the provisions at 52.212-3. All referenced clauses and
provisions are available on the Internet web at htt:/www.arnet.gov/far.
Posted 05/22/00 (W-SN457500). (0143) Loren Data Corp. http://www.ld.com (SYN# 0252 20000524\44-0001.SOL)