COMMERCE BUSINESS DAILY ISSUE OF MAY 11,2000 PSA#2598Department of the Air Force, Air Force Materiel Command, HSW -- 311
Human Systems Wing, 311th HSW/PK, 8005 9th Street, Brooks AFB, TX,
78235-5353 66 -- HYDRAZINE DETECTOR -- MONITOR, CHEMICAL AGENT, NSN
6665-01-327-3869, P/N MVIP2170 OR EQUAL SOL
Reference-Number-FD2050-99-10040 DUE 052600 POC Dennis Clements,
Contract Specialist, Phone 536-2359/2664, Fax 536-3392, Email
dennis.clements@brooks.af.mil -- Dennis Clements, Contract Specialist,
Phone 536-2359/2664, Fax 536-3392, Email WEB: Visit this URL for the
latest information about this,
http://www.eps.gov/cgi-bin/WebObjects/EPS?ACode=R&ProjID=Reference-Num
ber-FD2050-99-10040&LocID=1183. E-MAIL: Dennis Clements,
dennis.clements@brooks.af.mil. This is a SOURCES SOUGHT SYNOPSIS (SSS).
Sources are being sought for a Hydrazine Detector to be used for
detection of toxic amounts of hydrazine vapor in a designated work
area. Currently, Zewellger Analytics, (formerly MDA Scientific, Inc.)
of Austin TX is the government_s source for this acquisition, NSN
6665-01-327-3869, P/N MVIP2170. Be advised this is not a RFP and this
SSS in no way obligates the Government to award a contract. The
Government will not compensate any interested party, firm, or
individual that responds to this SSS. The United States Air Force, Air
Materiel Command, 311 Human Systems Wing, Brooks AFB, TX intends to
procure this acquisition as a sole source acquisition unless it is
ascertained that other qualified sources are available based on the
minimum, qualified hydrazine detector performance characteristics
listed below. If qualified sources are ascertained, the government will
seek to procure this acquisition competitively. Interested parties are
required to provide information/data in accordance with the
characteristics listed below so that the Government may evaluate to
ensure compliance. Detector volume: 1815 cubic inches. Detector weight:
25 Pounds. Recording mechanism volume: 57 cubic inches. Recording
mechanism weight: 3.75 pounds. Recording mechanism time: 200 hours.
Recording mechanism printing range: 0 to 1.0 parts per million (ppm),
in 0.1 ppm increments. Safety enclosure: no more than 110% combined
volume of detector and recording mechanism. Be designed for use in
hazardous or combustible environments. Electrical: 120Vac +/-10%, 50-60
Hz, 35 watts. Hydrazine detection range: 0 to 1.0 ppm, in 0.1 ppm
increments. Detection accuracy: + 10%. Repeatability: Better than +/-5%
at TLV. Display: illuminated digital or analog. Time to alarms
minimums: Hydrazine Concentrations vs Time to Alarm. 2.0 ppm/ 10
seconds; 1.0 ppm/ 20 seconds; 0.5 ppm/ 40 seconds; 0.1 ppm/ 200
seconds. Maintenance: No shorter than six-month increments. Sampling
distance: up to 100 feet. Output: Audible to 90 dB plus 4-20 mA,
RS232/RS4422. Operating temperature Range: 32-104 degrees F. All
potential offerors should contact the buyer/POC identified in this
notice for additional information and/or to communicate concerns, if
any, concerning this acquisition. Responses may be e-mailed to the
Dennis C. Clements at dennis.clements@brooks.af.mil or faxed to
210-536-3392. Responses received after 26 May 00 may be returned to
sender. If the buyer or contracting officer does not satisfy your
concerns, an Ombudsman has been appointed to hear concerns from
offerors or potential offerors during the proposal development phase of
an acquisition. The Ombudsman does not diminish the authority of the
program director or Contracting Officer, but communicates Contractor
concerns, issues, disagreements, and recommendations to the appropriate
Government personnel. When requested, the Ombudsman shall maintain
strict confidentially as to the source of the concern. The Ombudsman
does not participate in the evaluation of proposals orin the source
selection process. Interested parties are invited to call the Brooks
AFB Acquisition Ombudsman, Stephen Plaisted at 937-255-9005 or send
E-mail to: stephen.plaisted@ascsy.wpafb.af.mil. Posted 05/09/00
(D-SN453096). (0130) Loren Data Corp. http://www.ld.com (SYN# 0298 20000511\66-0016.SOL)
66 - Instruments and Laboratory Equipment Index Page
|
|