COMMERCE BUSINESS DAILY ISSUE OF MAY 10,2000 PSA#2597Department of the Air Force, Air Combat Command, 1st CONS, 74 Nealy
Avenue, Suite 100, Langley AFB, VA, 23665 41 -- PURCHASE AIR HANDLER UNITS -- F44600-00-Q-0112 SOL
F44600-00-Q-0112 DUE 051700 POC Leonard Layon, Contract Specialist,
Phone 757-764-2587, Fax 757-764-7447, Email
leonardo.layon@langley.af.mil -- Patricia Ward, Purchasing Agent, Phone
(757)764-4766, Fax (757)764-7447, Email WEB: Visit this URL for the
latest information about this,
http://www.eps.gov/cgi-bin/WebObjects/EPS?ACode=P&ProjID=F44600-00-Q-0
112&LocID=203. E-MAIL: Leonard Layon, leonardo.layon@langley.af.mil.
This is a combined synopsis/solicitation for commercial items prepared
in accordance with the format in FAR 12.6 as supplemented with
additional information included in the notice. This announcement
constitutes the only solicitation; proposals are being requested and a
written solicitation will not be issued. PAPER COPIES OF THIS
SOLICITATION WILL NOT BE AVAILABLE. (ii) Solicitation F44600-00-Q-0112
is issued as a Request for Quote (RFQ). Written documentation will not
be issued for this request for quote. (iii) The solicitation is being
conducted under Simplified Acquisition Procedures (SAP) FAR Part 13.
This solicitation document and incorporated provisions and clauses are
those that are in effect through Federal Acquisition Circular 97-17.
It is the contractor_s responsibility to be familiar with applicable
clauses and provisions. (iv) The Standard Industrial Classification
Code is 5075. (v) Langley AFB plans to procure, on a name brand basis,
TRANE Air Handler Units (AHU) of various sizes. (vi) Thefollowing
requirements are applicable: CLIN 0001- TRANE AHU, model number
MCCA017, 22 Ton. For cooling, unit shall be capable of supplying 8800
CFM, at 65 gpm, with a pressure drop of 10.82 ftwg. Access door shall
be right hand. Cooling coil shall be 6 rows of 0.025_ tubes. Cooling
coil shall be capable of handling an EWT of 45F and an EDB of 80F with
a LDB of 55F. For heating, unit shall be capable of 460 MBH, at 22.5
gpm, with a pressure drop of 1.05 ftwg. Heating coil shall be capable
of handling an EWT of 140F and an EAT of 50F. Fan location shall be
over the cooling coil facing back over the unit to allow air supply to
flow over the unit. Return section shall be located in front of unit
coming in under supply air. Fan motor shall be 7.5Hp and 200/60/3. Fan
total static pressure shall be 1.95 inwg. Quantity: 2. CLIN 0002 --
TRANE AHU, model number MCCA017, 22 Ton. For cooling, unit shall be
capable of supplying 8800 CFM, at 65 gpm, with a pressure drop of 10.82
ftwg. Access door shall be left hand. Cooling coil shall be 6 rows of
0.025_ tubes. Cooling coil shall be capable of handling an EWT of 45F
and an EDB of 80F with a LDB of 55F. For heating, unit shall be capable
of 460 MBH, at 22.5 gpm, with a pressure drop of 1.05 ftwg. Heating
coil shall be capable of handling an EWT of 140F and an EAT of 50F. Fan
location shall be over the cooling coil facing back over the unit to
allow air supply to flow over the unit. Return section shall be located
in front of unit coming in under supply air. Fan motor shall be 7.5Hp
and 200/60/3. Fan total static pressure shall be 1.95 inwg. Quantity:
2. CLIN 0003 -- TRANE AHU, model number MCCA014, 19 Ton. For cooling,
unit shall be capable of supplying 7600 CFM, at 57.5 gpm, with a
pressure drop of 9.16 ftwg. Access door shall be left hand. Cooling
coil shall be 6 rows of 0.025_ tubes. Cooling coil shall be capable of
handling an EWT of 45F and an EDB of 80F with a LDB of 55F. For
heating, unit shall be capable of 288 MBH, at 20 gpm, with a pressure
drop of 0.61 ftwg. Heating coil shall be capable of handling an EWT of
140F and an EAT of 50F. Fan location shall be over the cooling coil
facing back over the unit to allow air supply to flow over the unit.
Return section shall be located in front of unit coming in under supply
air. Fan motor shall be 7.5Hp and 200/60/3. Fan total static pressure
shall be 1.83 inwg. Quantity: 1 . CLIN 0004 -- TRANE AHU, model number
MCCA014, 18 Ton. For cooling, unit shall be capable of supplying 7200
CFM, at 55 gpm, with a pressure drop of 8.45 ftwg. Access door shall
be left hand. Cooling coil shall be 6 rows of 0.025_ tubes. Cooling
coil shall be capable of handling an EWT of 45F and an EDB of 80F with
a LDB of 55F. For heating, unit shall be capable of 273 MBH, at 18
gpm, with a pressure drop of 1.24 ftwg. Heating coil shall be capable
of handling an EWT of 140F and an EAT of 50F. Fan location shall be
over the cooling coil facing upward to allow air supply to flow up and
back over the unit. Return section shall be located in front of unit
coming in under supply air. Fan motor shall be 7.5Hp and 200/60/3. Fan
total static pressure shall be 1.7 inwg. Quantity: 1 .CLIN 0005 --
TRANE AHU, model number MCCA010, 11 Ton. For cooling, unit shall be
capable of supplying 4400 CFM, at 32.5 gpm, with a pressure drop of 5.3
ftwg. Access door shall be left hand. Cooling coil shall be 6 rows of
0.025_ tubes. Cooling coil shall be capable of handling an EWT of 45F
and an EDB of 80F with a LDB of 55F. For heating, unit shall be capable
of 167 MBH, at 11 gpm, with a pressure drop of 0.99 ftwg. Heating coil
shall be capable of handling an EWT of 140F and an EAT of 50F. Fan
location shall be over the cooling coil facing back over the unit to
allow air supply to flow over the unit. Return section shall be located
in front of unit coming in under supply air. Fan motor shall be 5.0Hp
and 200/60/3. Fan total static pressure shall be 1.6 inwg. Quantity: 2.
CLIN 0006 -- TRANE AHU, model number MCCA006, 8 Ton. For cooling, unit
shall be capable of supplying 3200 CFM, at 25 gpm, with a pressure
drop of 3.98 ftwg. Access door shall be left hand. Cooling coil shall
be 8 rows of 0.025_ tubes. Cooling coil shall be capable of handling an
EWT of 45F and an EDB of 80F with a LDB of 55F. For heating, unit shall
be capable of 121 MBH, at 9 gpm, with a pressure drop of 0.78 ftwg.
Heating coil shall be capable of handling an EWT of 140F and an EAT of
50F. Fan location shall be over the cooling coil facing back over the
unit to allow air supply to flow over the unit. Return section shall
be located in front of unit coming in under supply air. Fan motor shall
be 5.0Hp and 200/60/3. Fan total static pressure shall be 2.03 inwg.
Quantity: 1 (vii) Delivery date: 10 June 2000, FOB _ Destination.
(viii) The provision at FAR 52.212-1, Instructions to Offerors-
Commercial, applies to this acquisition. (ix) N/A. (x) Offerors are
reminded to include a completed copy of the provision at 52.212-3,
Offeror Representations and Certifications Commercial Items and
252.212-7000, Offeror Representations and Certifications Commercial
Items with its offer. (xi) Clause 52.212-4, Contract Terms and
Conditions- Commercial Items, is hereby incorporated by reference.
(xii) Clause 52.212-5 (Deviation) Contract Terms and Conditions
Required to Implement Statutes or Executive Orders- Commercial Items,
52.222-3 Convict Labor, 52.222-20 Walsh-Healey Public Contracts Act,
52.222-21 Prohibition of segregated facilities, 52.222-26 Equal
Opportunity (E.O. 11246), 52.222-35 Affirmative Action for Disabled
Veterans and Veterans of the Vietnam Era (38 U.S.C. 4212), 52.222-36
Affirmative Action for Workers with Disabilities (29 U.S.C. 793),
52.222-37 Employment Reports on Disabled Veterans and Veterans of the
Vietnam Era, 52.233-3 Protest After Award, 52.225-13 Restrictions on
Certain Foreign Purchases, 52.232-33 Payment by Electronics Funds
Transfer- Central Contractor Registration, 252.212-7001 (Deviation)
Contract Terms and Conditions Required to Implement Statutes or
Executive Orders Applicable to Defense Acquisitions of Commercial Items
and 252.204-7004 Required Central Contractor Registration, are hereby
incorporated by reference. (xiii) N/A (xiv) N/A (xv) N/A (xvi) Offers
may be faxed to 1 CONS/LGCV at (757) 764-7447, or mailed to 1
CONS/LGCV, 74 Nealy Ave., Langley AFB. All offers are due by 4:00 PM
Local Time, 17 May 2000. (xvii) For further information regarding this
solicitation, contact Leo Layon or Patricia Ward, Contract
Administrator @ phone: (757) 764-4766. Collect calls will not be
accepted, e-mail: patricia.ward@langley.af.mil. Posted 05/08/00
(D-SN452565). (0129) Loren Data Corp. http://www.ld.com (SYN# 0188 20000510\41-0002.SOL)
41 - Refrigeration, Air Condition and Air Circulating Equipment Index Page
|
|