COMMERCE BUSINESS DAILY ISSUE OF JULY 23,1999 PSA#2394Contracting Office, P.O. Box 1609, Oceanside, Ca 92051-1609 44 -- BOILERS. 30 HORSEPOWER SOL M00681-99-T-0309 DUE 073099 POC
Contract Specialist, Gloria Muchemore 760-725-1937 This is the first
correction to the combined synopsis/solicitation appearing July 16 1999
for furnace, steam plant, drying equipment and nuclear reactors.
Referencing M00681-99-T-0309. Solicitation to include additional
specifications as follows; minimum heating surface; 125 sq. ft.,
minimum furnace folume; 18.7 du. ft., design pressure; 30 PSI water,
fuel; natural gas @ 14"WC, maximum width with gas train; 55", maximum
overall length; 100", maximum height with trim; 70", supply size; 4",
return size; 4", drain size; 1", stack diameter; 10"OD, safety relief
valve set at 30 PSI, pressure/temperature gauge; 4.5", blower; 120volt,
1 phase, 60 hertz, ignition type; gas pilot. Operating & high limit
pressure/temperature controls, vertical stack outlet, front and rear
smoke boxes must be flanged and detachable from the boiler. ASME and
CSD-1 approval, factory mounted, wired and tested Gordon-Piatt #R8-G-05
Burner, registered with the National Board of Boiler Inspectoes. Class
code is 44 -- furnace, steam plant,drying equipment and nuclear
reactors. Change Award date to read 6 August 1999. Offers are now due
by 30 July 1999. Delivery date is 30 days ARO. Posted 07/21/99
(W-SN357400). (0202) Loren Data Corp. http://www.ld.com (SYN# 0307 19990723\44-0001.SOL)