COMMERCE BUSINESS DAILY ISSUE OF MAY 21,1999 PSA#2351Contracts Group, Bldg 588, Mail Stop 32, Naval Air Warfare Center
Aircraft Division, Patuxent River, MD 20670-5304 41 -- REFRIGERATION, AIR CONDITIONING, AND AIR CIRCULATING EQUIPMENT
WITH COMMERCIAL BLOWER SYSTEM SOL N00421-99-Q-1587 DUE 060799 POC
Contact, Angela Franco, Phone (301) 342-1825 x107 E-MAIL:
francoa@navair.navy.mil, francoa@navair.navy.mil. This is a notice of
intent to Request a Proposal and negotiate with Joos Equipment Compay,
PO Box 368, Paoli, Pennsylvania 19301 on an other than full and open
competitive basis. The Naval Air Warfare Center Aircraft Division,
Propulsion System Evaluation Facility, Patuxent River, MD has a
requirement for a Blower System with integral discharge heat exchanger
and controls, to provide conditioned air to an altitude test chamber.
The system must utilize Hoffman model 17903 centrifugal blower
machinery to maintain compatibility with existing test cell exhauster
machinery and must meet the requirements listed in the rating table
below. As such, Joos Equipment Company has been identified as the only
responsible source capable of meeting the Government's requirements.
The government requires the system to be tested by the manufacturer
prior to delivery and the test to be witnessed by the government. The
required delivery schedule is 120 days after award of order. This
acquisition is being procured in accordance with the Federal
Acquisition Regulation (FAR) Part 12, as such a SF 1449 shall be
issued. Further, this procurement is being processed in accordance with
the Simplified Acquisition Procedures, Part 13 of the FAR. This action
is set-aside for small businesses. The applicable SIC code is 3564 and
the small business size standard is 1,000 employees. The government
intends to procure this system on a firm-fixed price basis. The only
manufacturer capable of providing the required parts/system is Joos
Equipment Company, Address: Station Square 2, North Valley Road, Paoli
PA 19301; Mailing Address: PO Box 368, Paoli PA 19301. Any quotes
submitted within 15 days will be considered. IMPORTANT INFORMATION FOR
PROSPECTIVE CONTRACTORS: DFARS 252.204-7004 "Required Central
Registration" applies. Registration in the DODs Central Contractor
Registration (CCR) database will be a prerequisite for receiving an
award resulting from this combined synopsis/solicitation. For more
information on the CCR, contact the CCR Assistance Center at
1-888-227-2423 or http://ccr.edi.disa.mil. All matters regarding this
requirement should be addressed to Ms. Angela Franco at: Contracts,
AIR-2.5.4.3.1.4 Bldg 588 Suite 2, NAWCAD, 47253 Whalen Road Unit 588,
Patuxent River, MD 20670-1463 or by phone at (301) 342-1825 ext. 107,
fax (301) 342-1864/1847, or via the internet at
FrancoA@NAVAIR.NAVY.MIL. RATING TABLE FOR BLOWER SYSTEM RATING AIRFLOW
INLET TEMP INLET PRESS DISCH TEMP DISCH PRESS Lb/sec F total
inHgA total F total inHgA total A 10 120 29 100 30 B 22 120 29
100 30 C 22 120 29 100 40 D 22 10 31 100 40 E 20 100 * 100 60 *Inlet
pressure determined by outlet pressure of first blower when two blowers
are staged Rating Table Notes All notes are binding for all rating
table conditions. 1. The system shall be capable of achieving airflow
rates and discharge conditions stated in The Rating Table with the
relative humidity of the air that enters the system ranging from 0% RH
to 100% RH, except that capabilities will not be required at specific
humidity greater than .02 pounds of water per pound of dry air. 2. The
system shall have stable operation for the operating points listed in
The Rating Table. In steady state mode at any given flow rate through
the system, the discharge pressure shall not fluctuate more than a
total variation of 2.0 in Hg. 3. The system shall be capable of
changing from any one Rating condition to any other Rating condition
within 30 seconds of total elapsed time. 4. All ratings are based upon
the assumption of customer furnished cooling water supplied to the
system at a temperature of 80F. Posted 05/19/99 (W-SN333504).
(0139) Loren Data Corp. http://www.ld.com (SYN# 0227 19990521\41-0001.SOL)
41 - Refrigeration, Air Condition and Air Circulating Equipment Index Page
|
|