COMMERCE BUSINESS DAILY ISSUE OF MARCH 4,1999 PSA#2295Commanding Officer, NAVFACCO, Bldg 41 Code 27, NAVFACENGCOMDET-SLC,
4111 San Pedro Street, Port Hueneme, CA 93043-4410 J -- SERVICES REQUIRED FOR CLEANING OF INDUSTRIAL BOILERS SOL
N47408-99-Q-1521 DUE 031599 POC Debra Buckley, Purchasing Agent, (805)
982-3993 This procurement is for services to clean. This is a combined
synopsis/solicitation for commercial services prepared in accordance
with the format in Subpart 12.6, as supplemented with additional
information included in this notice. This announcement constitutes the
only solicitation; proposals are being requested and a written
solicitation will not be issued. N47408-99-Q-1521 is issued and a
request for quotation (RFQ). This solicitation document and
incorporated provisions and clauses are those in effect through Federal
Acquisition Circular FAC 97-03. CLIN 0001: QUANTITY (1 Lot);
DESCRIPTION: Provide services for cleaning of Boilers No. 1, 2, and 3
in accordance with the following Statement of Work: Background:
Accumulated scale on the inside walls of the steam and water/mud drums
of Boilers No. 1, 2 and 3 needs to be removed. A qualified
boiler/industrial service company needs to be contracted to remove the
previously mentioned scale. Boiler No. 1, 2 and 3 name plate data and
other specifics: MFG. BABCOCK & WILCOX BUILT 1941 TYPE: INTEGRAL
FURNACE BOILER SER.#'s: 12328, 12329 and 12330 S/N: 0105-003-000 CAP:
50,000 DES. PR.: 450 LBS OPR. PR.: 430 LBS STEAM TEMP: 600F
FUEL: Nat. Gas and #6 FUEL OIL STEAM DRM.: 53-7/8in diameter 21ft,
8-3/8in length WATER DRM.: 35-5/8in diameter 18ft, 9-1/8in length
BOILER WET: 5700 gallons CAPACITY TECHNICAL QUALIFICATIONS: Contractor
shall have at least 5 years experience in Industrial Boiler repairs
and cleaning. Contractor must presently hold "U", "R", "S" Code stamps.
All personnel doing work on the cleaning project shall be trained and
up to date in confined space and personal protective equipment
procedures. ACTUAL WORK STATEMENT: Remove all scale deposits in steam
and water/mud drums of Boilers No. 1, 2, and 3. The work shall be
performed in the following steps: 1. Perform lock out/tag out for
object equipment. Object equipment includes fuel lines (Nat. Gas and
No. 6 Fuel Oil), steam lines and feedwater lines. 2. Open boiler
waterside and firesides. 3. Obtain confined space entry permit from
local activity. 4. Remove steam drum internals prior to cleaning. 5.
Clean steam and water/mud drums by sodium bicarbonate blasting. 6.
Visually inspect steam and water/mud drums 7. Replace any removed steam
drum internals after NFESC personnel have completed nondestructive
examination of drums. 8. Close boiler waterside and firesides. 9.
Remove lock out/tag out. All work performed shall be coordinated
between MCRD, Parris Island Central Energy Plant, SC and NFESC
personnel. Boilers will be cleaned on separate days and in conjunction
with NFESC nondestructive testing of steam and water/mud drum
internals. PERIOD OF PERFORMANCE: Field work is to be performed between
the dates of 22 March and 2 April 1999. This time period is to include
initial setup and break down once the work is completed. FAR
Provisions 52.212-1 and 52.212-2, Evaluation-Commercial Items applies.
Evaluation criteria will be technical capabilities, price, past
performance. Offerors are to include a completed copy of FAR Provision
52.212-3, Offeror Representations and Certifications-Commercial Items,
with its offer. FAR Clause 52.212-4, Contract Terms and
Conditions-Commercial Items, applies as well as FAR Clause 52.212-5,
Contract Terms and Conditions Required to Implement Statutes or
Executive Orders-Commercial Items. The following FAR clauses cited in
52.212-5 apply: 52.222-26, 52.222-35, 52.222-36, 52.222-37, 52.222-41,
52.222-42. Request for Quotation (RFQ) number is N47408-99-Q-1521.
Quotes are due NLT March 15, 1999, 4:30PM (PST). Submit quotes to
Officer in Charge, NAVFACENGCOMDET-SLC, Attn: Debra Buckley, Contracts
Office, Code 2716, Bldg. 41, 4111 San Pedro St., Port Hueneme, CA
93043-4410 or by FAX (805) 982-3015, Attention Debra Buckley. Posted
03/02/99 (W-SN303952). (0061) Loren Data Corp. http://www.ld.com (SYN# 0039 19990304\J-0002.SOL)
J - Maintenance, Repair and Rebuilding of Equipment Index Page
|
|