COMMERCE BUSINESS DAILY ISSUE OF AUGUST 18,1998 PSA#2161US Army Corps of Engineers, Nashville District, PO Box 1070, Nashville,
TN 37202 28 -- DIESEL POWER GENERATORS SOL DACW62-98-Q-0040 DUE 082098 POC
Kristal R. Jones, Contract Specialist, (615)736-7276; Peggy E. Owen,
Contracting Officer, (615)736-5679. AMENDMENT: This amendment is issued
to resubmit the entire description with changes; ( double parentheses
show changes. SPECIFICATIONS: The generator shall have a rated capacity
350 KW, 437.5 KVA at 0.8 PF, variable voltage; three phase 60 hertz,
1800 rpm, 277/480-volt; reconnectible 12-leads,((1200 amp mainline
circuit breaker for 240V AC with 600 amp trips for 480V AC operation,
multi-voltage distribution panel with quick change board wired to
generator leads to obtain 240 or 480 voltages (stud connectors for 240V
AC, bus bar connector for 480V AC). The unit shall have receptacles and
individual circuit breakers for single phase voltage including (1) 240
volt, 50 amp, (2) 120 volt 15 amp duplex, (2) 120 volt 20 amp twist
lock; remote start-stop contacts for use with automatic transfer
switches)), 24-volt negative ground complete with two 12-volt batteries
rated minimum 700 cold cranking amps at 0 degrees Fahrenheit. The
engine shall be diesel 6 cylinder, 4-cycle turbo charged/after cooled
cast iron cylinder block with replaceable wet liners and radiator
cooled. A Woodard Electronic governor for ishochronous operation (0%
droop). The generator monitoring system shall include the following
indicators and gauges: over-speed shutdown, over-crank shutdown, high
coolant temperature shutdown, low oil pressure shutdown, pre-warning
for high coolant temperature, pre-warning for low oil pressure, low
fuel indicator, run and switch off lights, engine oil temperatur gauge,
tachometers, fuel pressure gauge, automatic start/stop. The generator
shall be self-ventilating, brushless excitations, flexible disk
coupling, amortisseur type windings. The generator shall be designed
and manufactured to meet the requirements of NEMA, ANSI, IEEE where
applicable. The metering system shall include AC voltmeter, AC ammeter,
(dual range indicating current each phase), high/low meter scale
indicator for broad range connection indication, voltmeter/ammeter
phase selector with off position, frequency meter, console mounted
rheostat +/-5% voltage adjustment, 24 volt starting system with
automatic battery charger, ((an engine driven 24 volt DC alternator
separate from automatic battery charger)) and jacket water heater for
cold starts. The fuel system shall store 350 gallons minimum to provide
eight hours continuous operation at full load ((and 450 gallons minimum
for 16 hours)). The cooling system shall have a sufficient capacity of
engine coolant to operate satisfactorily in temperatures from -20
degrees Fahrenheit to 125 degrees Fahrenheit. The housing shall be a
waterproof enclosure made of ((12 gauge sheet metal)) with factory
installed exhaust silencer designed to allow ample air exchange and to
be mounted to the generator's standard mounting base and radiator
cooling. The enclosure shall be designed to have accessible openings so
that all components may be easily serviced and maintained and be sound
attenuated 100 dba at 50 feet. The trailer shall be constructed for
highway and off-road transportation with sufficient rating to carry the
genset, fuel and all accessories and must be stable when towed at
highway speeds. All DOT required lights and brakes for highway
transportation shall be installed. ((These units shall be EPA and CARB
certified to meet 1996 and current emissions standards for mobile
off-highway applications.)) Three sets of technical publications
containing operator's instructions, lubrication charts, parts list,
maintenance, service and repair information shall be included. RFQ
Submission Date: RFQ submiital date has been extended to 20 August
1998. Posted 08/14/98 (I-SN237173). (0226) Loren Data Corp. http://www.ld.com (SYN# 0243 19980818\28-0009.SOL)