COMMERCE BUSINESS DAILY ISSUE OF AUGUST 13,1998 PSA#2158Contracting Officer, RLR VA Medical Center, 1481 West 10th Street,
Indianapolis, IN 46202 J -- CHANGING FILTERS & CLEANING FAN COILS AND AIR HANDLERS SOL
583-84-98 DUE 091098 POC Joyce Miller 317-554-0207 This combined
synopsis/solicitation for commercial items prepared in accordance with
the format in Subpart 12.6, as supplemented with additional
information included in this notice. This announcement constitutes the
only solicitation; quotations are requested and a written solicitation
will not be issued. Solicitation 583-84-98 is issued as a request for
quotation (RFQ). The solicitation document and incorporated provisions
and clauses are those in effect through Federal Acquisition Circular
97-04. This is a competitive commercial items procurement under the
Standard Industrial Classification (SIC) Code 7349 and Small Business
Size Standard of $12.0 Million per annum. The VA Medical Center,
Indianapolis, Indiana intends to contract for changing filters and
cleaning on all fan coil units (450), air handler units (47) and other
self contained units and all other systems requiring change for the
period of October 1, 1998 through September 30, 1999 with four option
years. Work to be performed at the VA Medical Center, 1481 West 10th
Street, Indianapolis, IN 46202. Contractor shall provide pricing for
base year and all four (4) option years. Contractor will furnish all
labor necessary to change all ashrae filters 80% to 95% efficient in
units located in basement, 3rd floor, 5th floor and remote roof area.
Contractor will change filters on ac-1 through ac-47 and all return
fans and exhaust fans, with like filters that meet current applicable
codes. Contractor will change 4" pleat 30% efficient filters on a/c
units 26 through 47 in area "A" wing every 60 days and change 2" pleat
30% efficient in front of high efficient filters at 20 separate
locations four times a year. Change 81-2" poly pad filters in a/c units
#1 through #6 monthly; twice yearly change out the hepa filter 99.99%
filters in isolation rooms and t.b. rooms at 20 separate locations.
This will be done as needed by pressure difference across the filter.
Contractor will take appropriate infection control measures to remove,
dispose of, and replace subject filters; Contractor shall testat ac
37a and 37b annually replace (18) 24 x 24 and (6) 12 x 24 99.97% hepa
high capacity efficiency filters. Each filter shall be individually
tested and certified for efficiency and initial resistence using a
penetrometer for 0.3 micron hot dop test (dos testing available), or
dual laser spectrometer for test at specific particle sizes. In
addition, automatic scanning equipment shall be used to verify
leak-free filters. Documentation of test data shall be supplied on
individual labels on each filter enclosing frame.; Vendor will provide
weekly updated documentation to engineering operations supervisor
which indicates the date and locations that filters were replaced.
Vendor will also install stickers at all filter replacement locations
as approved by operataions supervisor; vendor shall provide all
equipment, materials and labor to perform annual surgical room air
cleanliness testing and performance certifications per fed std# 209e
and hepa testing per nsf std #49 and i.e.s. rps as applicable. Surgical
unit consists of 10 surgical suites and (18) hepa filters in upstream
filter housing(s). Differntial laser particulate counts at minimum
number of locations to provide statistical validity of room cleanliness
classification per fed std 209e. Counts taken at 2 levels for operating
thearers, 1 level for entire rooms. Minimum of 3 to 5 replicate counts
per location. Location of o.r. rooms#, description, room size (sq ft.)
A-4115m cysto, 333, a-4110, o.r.#9, 380, a-4070, o,r.#1, 725, a-4076,
o.r.#2, 684, a-4079, o.r. #3, 440, a-4082, o.r. #4, 396, a-4083, o.r.
#5, 396, a-4086, o.r. #6, 625, a-4088, o.r.#7, 660, a-4091, o.r.#8, 485
vendor will provide assistance and methodology training installing new
filters at no charge. Vendor will perform hepa filter integrity test
and leak testing of hepa filters. (photometric probe of down stream
side of hepa filter banks using concentrated upstream challenge.)
.vendor will perform air flow velocity and room air changes in each
o.r. room. Vendor will perform room differential pressure test in each
o.r. room accurate to 1/1000" w.g. vendor will rpovide 4 copies of a
written performance testing and certification report to the engineeirng
operations supervisor documenting the above test results.. Sic code
7349 applies. Request for service calls will be made only by the COTR
or designee thereof. Maintenance shall be performed during regular
working hours which are 0800 to 1630, Monday through Friday, excluding
legal holidays which are New Years Day, Martin Luther King's Birthday,
Presidents' Day, Memorial Day, Fourth of July, Labor Day, Columbus Day,
Veterans' Day, Thanksgiving and Christmas Day. No work shall be
performed or billed outside the hours specified. In the performance of
this contract, the Contractor shall take such safety precautions as
the Contracting Officer or COTR may determine to be reasonably
necessary to protect the lives and health of the occupants of the
building. The absence of such provisions shall cause a notice of
non-compliance to be issued. The Contractor shall, after receipt of
this notice, immediately correct the conditions which are deficient.
Payment shall be made quarterly in arrears, upon receipt of a proper
invoice. Invoices shall be submitted in accordance with Federal
Acquisition Regulation 52.212-4(g) and shall be submitted to Chief,
Fiscal Service 04(d), VA Medical Center, 1481 West 10th Street,
Indianapolis, IN 46202. The provisions at FAR 52.212-1, Instructions to
Offerors-Commercial Items applies to this acquisition with the
following changes: items (e) and (h) of the standard clause are
deleted. Offerors shall include a completed copy of the provision at
FAR 52.212-3, Offeror Representations and Certifications-Commercial
Items, with their offer. The clause at FAR 52.212-4, Contract Terms and
Conditions-Commercial Items, applies to this acquisition. The clause at
FAR 52.212-5, Contract Terms and Conditions Required to Implement
Statutes or Executive Orders-Commercial Items, applies to this
acquisition which shall also include the following clauses: 52.203-6,
52.203-10, 52.219-8, 52.219-14, 52.222-26, 52.222-35, 52.222-36,
52.222-37 and 52.225-3. The following standard FAR and VAAR clauses are
incorporated and apply to this acquisition: 52.215-17, 52.217-8,
52.217-9 (which provides that the Government may extend the term of the
contract, provided that the Government shall provide a preliminary
notice of intent at least 60 calendar days prior to the expiration
date; and services under this contract shall not exceed five (5)
years), 52.232-18, 52.232-19(which provides that funds are not
authorized past September of any fiscal year, unless written
authorizations is received from the Contracting Officer), 52.244-6,
52.252-2, and VAAR 852.219-70, 852.270-1, and 852.270-4. Warranty of
service shall be in accordance with Standard Industry Practice in
effect at the time of award. Interested offerors may submit their
proposals along with a completed copy of the provision at FAR 52.213-3,
Offeror Representations and Certifications-Commercial Items, on or
before 1630, September 5, 1998. Quotations may be provided to the
Contracting Officer at the address above or Fax to (317) 554-0200.
Posted 08/11/98 (W-SN235465). (0223) Loren Data Corp. http://www.ld.com (SYN# 0079 19980813\J-0029.SOL)