COMMERCE BUSINESS DAILY ISSUE OF AUGUST 3,1998 PSA#2150U.S. Environmental Protection Agency, Contracts Unit, 100 Alabama
Street,S.W., Atlanta, GA 30303 66 -- CUSTOM WALK-IN PM 2.5 FILTER WEIGHTING AND CONDITIONING ROOM SOL
EPA-98-037 DUE 081498 POC Nancy M. Watkins, 404-562-8377 The U.S.
Environmental Protection Agency intends to negotiate with Equitech of
Georgia, Inc. for National PM2.5 Filter Conditioning and Weighing Lab.
PM2.5 Filter Weighing and Conditioning Laboratory Specifications:
Temperature: Range 20-23degrees C; precision 2 degrees C over 24 hours
Humidity: Range 30-40%RH; precision 5%RH over 24 hours Room Size: 12W
x 12D x 8'2"H (Inside Dimension) 12'8"W x 12'8"D x 8'6"H (Outside
Dimension) These controls must be met with one to two people within the
room for work periods up to 2-4 hours per day. There will be a minimum
of 4-6 entries into room over 24 hours. Description: Room within a
Room Installation 1. Free Standing structure of 4 inch thick urethane
panels on screeds. Walls erected on existing floor. Insulation: "K"
factor = 0.121 -- 0.125 "U" factor = 0.030 -- 0.031 "R" value = 30 2.
Colored textured finish on interior and exterior walls. 3. Right hinged
entry door 34 inch by 78 inch with l4 inch by 24 inch viewport window.
4. Mechanical systemcomprised of Air Cooled Condenser/Compressor a.
Humidification by steam generator b. Dehumidification by desiccant
dryer c. No on-roof or outside installation. All systems must be
install within a larger room which can be controlled at the target
temp/RH levels 10 percent. All mechanical units located on top of the
structure. 5. Control panel mounted outside door with microprocessor
based temperature/ humidity recorder with digital display, audible
alarm, SPST alarm/relay contact, data logger and user selectable 24
hour or 7-day chart (Dickson TH 603). The recorder must have the
following: NIST Traceable Calibration, 3-points Software for
downloading data, cable and manual Calibration Kit 180, 24-hour Charts,
0 degree -- 50 degrees C Pens (3-red and 3-blue). 6. Provide sump and
pump to remove condensate from the mechanical units. 7. Ceiling panels
designed with diffusible membrane to create uniform (laminar) air
downflow with whole room temperature and humidity stability, and
minimum turbulence. 8. HEPA or equivalent type filter installed in air
recirculation path with standard outside air exchange. 9. Provide four
48 inch flourescent vapor proof fixtures with a minimum of 2 bulbs
each. 10. Provide 4 duplex outlets with exterior wiring connections to
a UPS. 11. Interior sound levels must be less than 65 dbs in the inner
and outer rooms 12. Provide connection for fire and emergency alarms.
13. Must accommodate at least one sprinkler head through the lab
ceiling. 14. Provide minimum warranties: 1 year general parts and labor
10 years on panels 4 years on comopressor and parts 15. Structure to be
installed and operational within eight (8) weeks from the requisition
date. Materials, Service and Labor To Be Provided: 1. Provide and
install component detailed above 2. Removal of crating materials 3.
Start-up and operational qualification of unit within specifications
above 4. Training of owner designated service personnel or responsible
person 5. Following the standard warranty period, provide service
contract for mechanical systems (4-6 above) Request for Quotation (RFQ)
EPA-98-037 will be issued for this requirement. The resulting award
will be on a purchase order. Interested parties who believe their
product can meet the requirements must submit a brief description of
the equipment capabilities for a determination as to suitability. All
responsible sources may submit a response for consideration. Posted
07/30/98 (W-SN230748). (0211) Loren Data Corp. http://www.ld.com (SYN# 0456 19980803\66-0012.SOL)