COMMERCE BUSINESS DAILY ISSUE OF JULY 13,1998 PSA#2135Region 10, Environmental Protection Agency, Office of Management
Programs, Acquisition Team, 1200 6th Avenue, Seattle, WA 98101 Z -- INSTALL HIGH EFFICIENCY PARTICULATE (HEPA) AIR FILTERED SUPPLY
SYSTEM SOL RFQ98HEPA DUE 081498 POC Maureen Bagocius, 206-553-8209. CO:
Patrick Brunner, 206-553-0326 E-MAIL: brunner.pat@epamail.epa.gov,
bagocius.maureen@epamail.epa.gov. Contractor to provide, install and
test a 1.5 ton self contained computer room air conditioner (Liebert or
approved equal). Unit shall have an air cooler condenser with a two
speed fan, 18,100 BTUH@ 675 CFM and 17,700 BTUH @ 565 CFM; 4.6 KW
electric reheat section, steam generator type de-humidifier with a
capacity of 2.5 lbs. Per hr. and a "HEPA" type filter to provide
maximum particulate control in the area to be served (ie..Munters
Dehumidifier w/HEPA Filter Part Number HC300); compressor hermetically
sealed with suction gas cooled motor, internal vibration isolation,
internal thermal overloads, suctions and discharge service valves,
manual reset high pressure switch, and pump down low pressure switch.
The room mean relative humidity should be held between 30-40%, with a
variability of not more than +/- 5% over a 24 hour period. Mean
temperature should be held between 20 and 23 degrees C, with a
variability of not more than +/- 2C over a 24 hour period. Relative
humidity and temperature must be measured and recorded on a daily basis
during equilibration (either manually or by hygrothermograph). Chassis
shall be constructed of steel with thermal and acoustical insulation,
removable service access panels, and provided with vibration
isolators. Micro processor temperature control with plastic membrane
key pad for set point and program control, seven day programming with
display, and clock display. A wall mounted temperature and humidity
recorder. The unit shall be a "Supco" model number CR4 universal
recorder or equal. The unit must provide two independent simultaneous
measurements of temperature and humidity at speeds of 31 days, 7 days,
24 hours, 12 hours, 6 hours, 3 hours or 1.5 hours. Unit shall operate
on standard 110VAC power and come with assortment of 6" diameter
charts and pens. The recorder must have a temperature recording range
of -40F to 170F, humidity recording range of 0 to 100% RH. Relative
humidity and temperature must be measured and recorded on a daily basis
during equilibration (either manually or by hygrothermograph).
Temperature measurements will be accurate to +/- 1C. Relative humidity
measurements will be accurate to +/- 2% RH. Installation address is:
EPA Region 10 Laboratory, Port Orchard, WA. Performance Period: 30 Days
from notice to proceed. Written Quotation required. "See Note 1".
Posted 07/09/98. (0190) Loren Data Corp. http://www.ld.com (SYN# 0198 19980713\Z-0046.SOL)