Navy Public Works Center, 310 John Tower Road, Pensacola, FL 32508-5303

61 -- PURCHASE OF AUTOMATIC TRANSFER SWITCH FOR DIESEL ENGINE GENERATOR SOL N65114-98-Q-F505 DUE 042998 POC Georgia M. Fils, 850 452-4187/fax 850-452-5088 Automatic Transfer Switch shall employ SF 6 dielectric gas. Minimum design voltage shall be 5KV, 1 minute withstand of 34 KV AC, continuous and loadbreak AMPS-200 AMPS. Impulse level (BIL) shall be 60 KV. Unit shall include all motor operators, controls and contacts required to integrate and function with the engine generator and the engine-generator circuit breaker. Overall dimension including motor operators shall not exceed 42" wide X 36" high X 30" deep. Please fax your request for a complete copy of the description of the Automatic Transfer Switch for Diesel Engine Generator to the attention of Georgia M. Fils @ 850 452-5088. Also, if you have any questions please put them in writing and fax them to me. (0104)

Loren Data Corp. http://www.ld.com (SYN# 0242 19980416\61-0006.SOL)