COMMERCE BUSINESS DAILY ISSUE OF MARCH 5,1998 PSA#2045Navy Public Works Center, 2730 McKean St, Ste 1, San Diego, CA
92136-5294 61 -- SOLID STATE FREQUENCY CONVERTERS SOL n63387-98-q-q032 DUE 031798
POC Tony Zamora, Supervisory Purchasing Agent, (619)545-9411, FAX:
(619)545-0243 E-MAIL: 836tzamo@pwcsd.nosc.mil, 836tzamo@pwcsd.nosc.mil.
2 EACH Solid state frequency converters, 180KVA, 400HZ:
stationary/vertical mounting. Meets or exceeds MIL-STD-704E, DFS-400,
DAC WZZ7364, BOEING D6-444588, SAE ARP 1940 and ARP 5015. Advanced
Diagnostic and Control System (ADCS), advanced state of the art
supervisory/diagnostic system. Checks all critical components prior to
supplying 400 HZ power, monitors all critical operation parameters
during operation, unit signals alarm and indicates potential problem if
parameters approach critical level during operation, unit shuts down
automatically if operation parameters of output characteristics fall
outside predetermined safe limits, diagnoses faults by identifying
cause and reporting prevailing conditions immediately prior to fault,
simplified user interface. Permits monitoring/testing of critical
circuits prior to and during operation. Fully automatic diagnostic
testing is performed each time the converter is started.
Specifications: inputs power 200 amperage @460 volts, 3 wire with
grounded service. Output: 180KVA (144KW continuous) @ 115/200 VAC, 3
PH, 400 HZ. Overloads (per ARP 1940): 125 percent for 10 minutes, 150
percent for 30 seconds, and 200 percent for 10 seconds. Overcurrent
protection: self-protection short circuit protection; will withstand
output short cleared by internal solid-state circuitry. MFG: HOBART
Model: 180SF200. Start-up and load test to be completed by a factory
technician or a factory authorized technician. Price to include
shipping to Naval Air station North Island in San Diego, CA. 1 LOT
Training on the operation and maintenance of the 2 EACH Solid State
Frequency Converters above for 10 personnel. Training to be conducted
by a factory technician or a factory authorized technician. Training to
be a one day session to be held at Naval Air Station North Island.
Exact training site will be determined upon award of contract. No
solicitation will be mailed out. Fax, mail, or E-Mail quotes will be
accepted. No telephone quotes will be accepted. See Numbered Note(s):
1. (0061) Loren Data Corp. http://www.ld.com (SYN# 0227 19980305\61-0001.SOL)
61 - Electric Wire and Power and Distribution Equipment Index Page
|
|