COMMERCE BUSINESS DAILY ISSUE OF JUNE 23,1997 PSA#1872DIRECTORATE OF CONTRACTING, ATZC-DOC, 1733 PLEASONTON ROAD, FORT BLISS,
TX 79916-6816 54 -- THIS IS A COMBINED SYNOPSIS/SOLICITATION FOR ELEVEN (11)
HAZARDOUS MATERIAL STORAGE UNITS. SOL DABT51-97-Q-0614 DUE 070297 POC
Purchasing Agent WILSON, SHARRY (915) 568-3423 (Site Code DOCSUP) This
is a combined synopsis/solicitation for commercial items prepared in
accordance with the format in Subpart 12.6, as supplemented with
additional information included in this notice. This announcement
constitutes the only solicitation; proposals are being requested and a
written solicitation will not be issued. Solicitation DABT51-97-Q-0614
is being issued as a request for quotation. This solicitation document
incorporates provisions and clauses are those in effect through
Federal Acquisition Circular 90-46. This acquisition is restricted to
small business. Standard Industrial Classification code is 3448. Items
are to be delivered and accepted at Fort Bliss, Texas. Exact location
to be made available at time of award. The following FAR Provisions
are applicable to this acquisition: FAR 51.212-1, Introduction of
Offerors-Commercial, applies to this acquisition and no additional
addenda applies. FAR 51.212-2 Evaluation-Commercial Items is applicable
as follows: The following factors shall be used to evaluate offers:
Technical, Delivery, Past Performance and Price. The lowest price,
technically acceptable product which meets the Government requirements
as listed in Line Items 1 through 9 will be considered. Delivery will
be evaluated on the contractors ability to initiate delivery within 30
days after receipt of order. Past Performance will be considered as it
related to the contractors inability to provide similar items. FAR
clause 52.212-3 Offeror Representations and Certifications-Commercial
Items (provide with offer). FAR clause 52.212-4 Contract Terms and
Conditions-Commercial Items. FAR 52.212-5 Contract Terms and Conditions
Required to Implement Statutes Or Executive Orders-Commercial Items.
The contractor will be asked to provide a warranty for the structures
that are consistent with customary commercial practices. The
solicitation is for Hazmat Storage Structures, in the configurations as
listed, using the Basic Structure Specifications (BSS) and Optional
Equipment Required (OER) descriptions located at the end of the line
item descriptions. LI0001 8'x10', Fire rated BSS 1a, 2a, 3, 4(230 GL
Sump), 5a, 6 through 13. OER Item 1-1 ea, 2-1 ea, 3-1ea, 4-48 lineal
ft, 5-80 sq ft. LI0002 8'x10', Fire rated, BSS 1a, 2a, 3, 4(230 GL
Sump), 5a, 6 through 13. OER Item 1-1 ea, 2-1 ea, 3-1 ea, 5-80 sq ft.
LI0003 10'x12', Fire rated, BSS 1a, 2a, 3, 4(380 GL Sump, 5a, 6 through
13. OER Item 1-1ea, 2-1 ea, 3-1 ea, 5-120 sq ft. LI0004 4' x 10' Not
Fire rated, BSS 1b, 2b, 3, 4(230 GL Sump) 5b, 6 through 13. OER Item
1-1 ea, 2-1 ea, 3-1 ea, 4-48 lineal ft. LI0005 10' x 20', Fire rated.
BSS 1a, 2a, 3, 4(670 GL Sump) 5a, 6 through 13. OER Items 1 1-ea, 2-2
ea, 6, 9 and 10. LI0006 10'x12', Fire rated, BSS 1a, 2a, 3, 4(380 L
Sump), 5a, 6 through 13. OER Items 1-1 ea, 2-1 ea, 4-66 lineal ft. 6
and 10. LI0007 10'x12', Fire rated, BSS 1a, 2a, 3, 4(380 GL Sump) 5a,
6 through 13. OER Items 1-2 ea, 2-1 ea, 3-1 ea, 4-66 lineal ft. LI0008
10'x20', Fire rated, BSS 1a, 2a, 3, 4(670 GL Sump), 5a, 6 through 13.
OER Item 1-2 ea, 2-2 ea, 3-2 ea, 4-122 lineal ft (61' in each
compartment) and 5-200 sq ft. LI0009 10'x20', Fire rated, BSS 1a, 2a,
3, 4(670 GL Sump), 5a, 6 through 13. OER Items 1-2 ea, 2-2 ea, 3-2 ea,
4-61 linealft (in only one compartment) 6, 7 and 8. LI0010 Delivery
and Off-Loading Charges in connection with the above items 1-9.
Specifications for Prefabricted Hazmat Storage Units. Basic Structure
Specifications: Free Standing, 9 ft high, re-locatable chemical storage
and containment structure. Must meet NFPA 30-1993 Fire Code for storage
of flammable and combustible liquids. Must meet Factory Mutual (FM)
approved 2-hour fire rating per ASTM E119 (ANSI/UL 263, NFPA 251)test
standard. One and one-half hour fire-damper on both intake and exhaust
of ventilation systems per NFPA requirements. UL classified; fuse
links to provide automatic closure in the event of fire. Includes the
following components for storage of flammable or combustible liquids
and other hazardous materials: 1a. Two (2) hour fire-rated gypsum on
interior walls and ceiling, protected by non-rusting, "galvannealed"
steel siding consisting of 12 gauge steel sheathing with 16 gauge
formed steel studs. 1b. Non-combustible walls consisting of 12 gauge
steel sheathing with 16 gauge formed steel studs. 2a. Two (2) hour
fire-rated roof structure consisting of 12 gauge steel deck with 16
gauge formed steel joists. 2b. Non-combustible roof structure
consisting of 12 auge steel deck with 16 gauge formed steel joists. 3.
1 1/8" thick coated plywood APA rated drum platform in removable
sections for easy access to the spill containment sump. Black enamel
painted 6" wide steel grating mount across the wall. 4. A (size as
specified on each LI listed above)gallon capacity, 2-hour fire rated
sump, continuously seam welded on interior and exterior; surpasses
regulatory and Factory Mutual (FM) requirements for spill containment.
5a. One (1) 54"x80" two hour fire-rated double steel wall door. Door
hardware includes a 3-point locking hardware includes a 3-point locking
system. 6. Naturaldraft ventilation. Each vent opening is equipped with
1 1/2 hour UL Classified fire dampers. The vent openings are arranged
to provide air movement and prevent accumulation of hazardous vapors.
7. Interior surfaces protected with a white chemical-resistant epoxy
coated finish. 8. Exterior surfaces finished with satin finish urethane
coating for high impact, corrosion, and abrasion resistance. 9. Static
grounding and bonding angles for prevention on explosive sparking
hazards. 10. Eight (8) ft grounding rod and cable shipped loose for
installation by owner. 11. Hazard labeling (DOT "Flammable" Placard,
NFPA 704 rating signs). 12. Four (4) inch riser for forklift and/or
crane slings and under sump inspections. 13. Four (4) hold-down angles
for bolting to owner's foundation for seismic and wind load anchoring.
Optional Equipment Required: 1. Removeable steel loading ramp (see LI
for quantity required). 2. Explosion-proof light, 150 watt (see LI for
quantity required). 3. Explosion-proof 350 cfm mechanical ventilator
(see LI for quantity required). 4. Steel shelving, 15" wide, in 3
tiers, on side and back walls (and partitions, where applicable)
adjustable (see LI for lineal ft required). 5. Sump line (see LI for SQ
FT required). 6. Exterior mounted dry chemical fire suppression system
with bell alarm system to central Fire Department (RF signal fire
alarm to be installed by owner). 7. Two (2) hour fire-rated partition
to divide structure in two compartments. 8. Additional two (2) hour
fire-rated 54"x80" double steel wall door, witha 3-point locking system
hardware. 9. R-11 insulation on walls and ceiling. 10. Explosion-proof
air conditioning unit rated at 14,500 BTU. The offers against this
solicitation are due 02 July 1997. Offers should be addressed as
follows: Regular mail: Directorate of Contracting, ATTN: Sharry L.
Wilson, ATZC-DOC-B(DOE), 1733 Pleasonton Rd., Fort Bliss, TX 79916. If
sent FEDEX or UPS use Directorate of Environment, ATTN: Sharry L.
Wilson, Bldg 624S, RM 131, Fort Bliss, TX 79916. The outside of your
offer must be marked with the RFQ number and indicate that it is only
to be opened by Sharry L. Wilson. No FAX or EDI offers will be
accepted. POC Sharry L. Wilson TEL (915) 568-3423. (0170) Loren Data Corp. http://www.ld.com (SYN# 0284 19970623\54-0002.SOL)