COMMERCE BUSINESS DAILY ISSUE OF MAY 21,1997 PSA#1850Social Security Administration, Office of Acquisition and Grants, 1710
Gwynn Oak Avenue, Baltimore, Maryland 21207-0696 K -- UPGRADE EXIDE EQUIPMENT DUE 070397 POC Patricia Bullock Tel:
410-965-9528 The Social Security Administration (SSA) intends to
negotiate a sole source contract with Exide Electronics, P.O. Box 190,
Franklinton, NC 27525, unless responses to this synopsis reveal that
other sources are capable of satisfying this requirement.The SSA
requires three (3) upgrades to the existing Exide 3000 Series --
Uninterruptible Power Supply (UPS) System. The SSA is seeking
information from qualified firms for three upgrades on twenty (20) 400
KVA series 3000 Exide modules in use at the National Computer Center
located in Baltimore (Woodlawn),Maryland. These upgrades involve
intergrating current production material, customization of SSA's
specialized UPS system and on-site design engineering support. UPGRADE
ONE (1): New High- Temperature "HT" Card Cage Logic Upgrade. This
enhancement involves the upgrade of all module card cage logic printed
circuit boards, transfer logic printed circuit boards, and spare parts
printed circuit boards. This upgrade covers a total of 272 card cage
logic (printed circuit card) assemblies and spare parts. This new logic
provides increased reliability and serviceability, due to higher
temperature components. UPGRADE TWO(2): Enhanced Gate Firing Module
(GFM) Circuit Assemblies -- This enhancement will upgrade all inverter
assembly ~leg~ GFM printed circuit assemblies, as well as an upgrade
of the harnessing that connect these assemblies to the card cage logic.
There is a total of 244 inverter leg gate firing modules (printed
circuit cards) assemblies required to perform the upgrade. In addition,
40 new customized shield wiring harnesses and 240 conversion kits are
needed. UPGRADE THREE (3): Fuse protected AC output filter upgrade --
This enhancement provides improved protection for both the output
filter capacitor banks and the UPS critical buss output. There is a
total of 20 customized AC output filter kit assemblies that are
required to perform the field upgrade. Organizations having the
required experience and the technical capabilities are invited to
submit complete documentation discussing such capabilities. See Notes
22 & 25. (0139) Loren Data Corp. http://www.ld.com (SYN# 0047 19970521\K-0001.SOL)