Loren Data Corp.

'

 
 

COMMERCE BUSINESS DAILY ISSUE OF MAY 14,1997 PSA#1845

Naval Surface Warfare Center, Carderock Division, 9500 MacArthur Blvd., West Bethesda, MD 20817-5700

61 -- BATTERY CHARGERS SOL N00167-97-D-0038 DUE 053097 POC Roger N. Branstiter (301) 227-3303 Please note the following corrections to the specifications spelled out in Block 17 of the initial announcement. (1) The area describing the rating of the equipment shall now read as follows, "The following rating shall apply to the units: Continuous full load, 100% duty cycle, 40 degrees Celsius ambient, 95% relative humidity." (2) The area describing the AC Input of the equipment shall now read as follows, "The following AC Input shall apply to the units: 480 (+ or -- 7.0%) volt rms, three-phase, 60 Hertz, ungrounded." (3) Under the area describing the Controls/Indicators, the item called Digital meters is changed to read as follows, "Digital meters (accuracy of + or -- 0.1% full scale, calibrated, with certification)". (4) Under the area describing the Electronic Controls, the sentence describing resolution is hereby changed to read as follows, "Sufficient resolution to permit setting voltage and current limits to within + or -- 0.5% of desired shall be provided". (5) Under the area describing the connections and wiring requirements, the sentence describing the fusing of remote DC sense leads is hereby changed to read as follows, "Remote DC sense leads shall be fused at less than or equal to 1A." All other information in the original synopsis is correct. (0132)

Loren Data Corp. http://www.ld.com (SYN# 0216 19970514\61-0009.SOL)


61 - Electric Wire and Power and Distribution Equipment Index Page