COMMERCE BUSINESS DAILY ISSUE OF APRIL 24,1997 PSA#1831Federal Prison Camp, Allenwood, Regional Contracting Office, P.O. Box
1000, Montgomery, PA 17752 46 -- WATER FILTRATION SYSTEM SOL RFQ 441-088 DUE 050697 POC Tom
Dufort, Regional Contract Specialist, 717-547-1641, extension 548 17.
Amendment No. 001: This is an amendment to the Request For Quotation
number 441-088 originally publicized in the CBD dated 4/08/97 and
hereby amends the STATEMENT OF WORK/SPECIFICATIONS with the following
additional information: This requirement is for a fresh water supply
system, not a waste water system. Each water filtration system will
consist of one tank with layers of gravel, sand, and carbon. The tanks
are each independent systems. The filter vessels require ASME stamps.
Access manholes are required in the filter vessels. Side mount valves
are acceptable. The total maximum height allowable is 90". Adequate
ceiling room in the building provides clearance to top load the media
into the vessel. The internal filter distributor is required to be
stainless steal. The quoter may provide an alternative quotation of a
corrosion-proof plastic or fiberglass tank which may be considered by
the Government. The external face piping is required to be copper. The
water to be filtered comes from the current domestic potable water
supply. The inflow to the system will be between the hours of 4AM and
8PM daily. The filter system does not require an influent pump.
"Centaur Carbon" is a brand trade name for granular activated charcoal.
An equal alternative to Centaur Carbon material is permitted. The
required delivery time is hereby changed to allow ninety (90) days from
the date of contract award. The Government will be responsible for
loading the filter media, if the media is required to be shipped
separately. If required for warranty purposes, the supplier will
supervise, at its expense, the loading of filter media and/or start up.
The following results were obtained from a water analysis report dated
August 5, 1996, for the subject domestic (city) water supply taken
from a kitchen tap: Alkalinity, M as CaCO3 mg/L: 24 Alkalinity, P as
CaCO3 mg/L: 0 Aluminum (Field Acidified) as Al mg/L: 1.9 Chloride as Cl
mg/L: 7 Conductivity -- umhos/cm: 196 Copper (Field Acidified) as Cu
mg/L: 0.01 Hardness, Calcium as CaCO3mg/L: 58 Hardness, Magnesium as
CaCO3 mg/L: 5 Hardness, Total as CaCO3 mg/L: 63 Iron (Field Acidified)
as Fe mg/L: 0.04 pH (Lab) Standard Units: 7.6 Phosphorus, Ortho as PO4
mg/L: <1 Silica as SiO2 mg/L: 6 Sulfate as SO4 mg/L: 45 Zinc (Field
Acidified) as Zn mg/L: 0.01 The hour and date specified for receipt of
quotes is extended to 2:00 PM EST, on May 6, 1997. Quoters must
acknowledge receipt of this amendment prior to the hour and date as
amended by acknowledging receipt of this amendment on each copy of the
quote submitted, or by separate letter or telegram which includes a
reference to the solicitation and amendment numbers. FAILURE OF YOUR
ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT
OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION
OF YOUR QUOTE. If by virtue of this amendment you desire to change a
quote already submitted, such change may be made by telegram or letter,
provided each telegram or letter makes reference to the solicitation
and this amendment, and is received prior to the opening hour and date
specified. Except as provided herein, all terms and conditions of the
document referenced herein, as heretofore changed, remains unchanged
and in full force and effect. Direct responses to the above address or
fax to the attention of Thomas G. Dufort at (717) 547-6819. (0112) Loren Data Corp. http://www.ld.com (SYN# 0221 19970424\46-0001.SOL)