COMMERCE BUSINESS DAILY ISSUE OF SEPTEMBER 4,1996 PSA#1672Contracting Officer (90C), VA Medical Center, 40 Industry Drive, West
Haven, CT 06516 66 -- HOT CELL SOL 689-135-96 DUE 092496 POC Mark Phillips,
203-937-3086 Supply and install a single Hot Cell F.O.B. destination to
the VA Connecticut Healthcare System, West Haven Campus, 950 Campbell
Avenue, West Haven, CT 06516. A Hot Cell is used in preparation of
radioactively labeled drugs. Outside dimensions of the hot cell shall
be approximately 59''w x 43''d x 95''h, and inside dimensions shall be
approximately 44''w x 33''d x 46''h. Front, side and rear walls, floor
and roof shall have not less than 60 mm lead shielding. Inside liner
shall be of seamless high quality stainless steel. A lead glass window
in the front door shall be at least 8''w x 12''h such that all
interior areas of the hot cell are visible with shielding equivalent to
60 mm lead and light transmission not less than 70%, and a protective
glass layer on both sides of the window. There shall be one exhaust
connection port in the roof of the hot cell 6'' in diameter. There
shall be one inlet connection port 4'' in diameter, at least one
stepped and plugged access port 2'' in diameter, an opening in the
floor for an ion chamber, and plugged mounting ports for manipulators.
It shall have a 12'' x 12'' sliding shielded door on each side, and
the front door opening shall be approximately 29''w x 24''h, with
access provided by overlapping sliding vertical panels (approximately
10''w x 24''h) operated manually with moderate effort.The hot cell
shall be equipped with a vapor tight lighting fixture. It shall be
equipped with at least four electrical outlets, fused and switched from
the main control panel individually or in pairs; four quick connect
fittings for utilities, with or without solenoid control from the main
control panel; a master control panel located either to one side of or
above the lead glass viewing port; and a cup sink, fitted with
appropriate trap or ball plug. Unit shall include steel support stand;
space under the hot cell shall be reserved for user's equipment, such
as vacuum pumps, detectors, power supply, etc.. Unit shall be provided
installed and functional, including appropriate user training. Requests
for solicitation package shall be in writing to the Contracting Officer
at the above address or Faxed to (203) 937-3089. SIC code 3841 applies.
(0243) Loren Data Corp. http://www.ld.com (SYN# 0310 19960903\66-0006.SOL)