Loren Data Corp.

'

 
 

COMMERCE BUSINESS DAILY ISSUE OF DECEMBER 15,1995 PSA#1491

Regional Contracting Department (Code 201B.DA), Fleet and Industrial Supply Center, Box 300, Pearl Harbor, HI 96860-5300

61 -- 500 KVA TRANSFORMER SOL N00604-96-Q-A003 DUE 122995 POC Contact Point: Debby Alberto, 808/474-2397, extension 202, Contract Specialist, Robert S. Kay, Contracting Officer This is a 100% ''small business manufacturers'' or ''small business dealers'', who can provide the product of a ''small business manufacturer'' set aside. FSC Code 6120, SIC code 3612, size standard 750 employees apply. 500 KVA substation transformer, insulated type, primary 4160V, secondary; 208y/120VAC, 3-phase, 4-wire, (4) externally operated 2-1/2% full capacity taps, (2) above and (2) below rated voltage, 11.5% impedance. Stainless steel diagram name plate and NEMA standard maintenance devices. The insulating liquid shall be mineral oil conforming to ASTM D 3487, type II, and shall be tested in accordance with ASTM D 117. Transformer shall be identified as non-pcb on name plate. New transformer shall fit into existing available space and conform to current electrical connection requirements. Existing transformer is General Electric secondary substation transformer model numbers F-957510A and F-957510B. Quantity: 2 each. FOB Pearl Harbor, Hawaii. Delivery: On or about February 22, 1996. All qualified sources may submit a proposal which shall be considered by the agency. Please fax your request for the solicitation package to 808/471-5750 or 808/474-8885 and include with your request your phone and fax number. (0347)

Loren Data Corp. http://www.ld.com (SYN# 0253 19951214\61-0005.SOL)


61 - Electric Wire and Power and Distribution Equipment Index Page