COMMERCE BUSINESS DAILY ISSUE OF OCTOBER 10,1995 PSA#144845CONS/LGCXA, 1201 Minuteman St, Patrick AFB, FL 32925-3237 61 -- UNINTERRUPTIBLE POWER SUPPLY SOL F08650-95-R-A255 DUE 102095 POC
Francis Ting, Contract Specialist, (407) 494-7091 John M. Hammerling,
Contracting Officer, (407) 494-7091. Item 0001, One diesel-supported
rotary uninterruptible power supply system (UPS). The UPS shall include
a 500 kVA, 400 kW, critical system rated, on-line, synchronous rotary
power conditioner coupled to a diesel engine and clutch with a
UPS/Engine control module, a separate 500 kVA, 400 kW, essential system
supplied by the motor of the rotary power conditioner during diesel
operation, automatic transfer switch for the essential load, UPS
batteries for at least three (3) minutes (''end of life'' rated)
support time at 25 degrees Celsius for 400 kW critical system load, DC
disconnect switch, maintenance bypass external to the UPS module,
remote annunciator panel, and all controls and accessories necessary
for the equipment to function properly as a system. Diesel operation
shall occur only on utility failures of greater than 5-second duration,
except for startup, testing, or manual initiation for load curtailment.
The diesel engine and clutch shall be standby rated to support the
critical load plus 10%, and the essential load plus 10%. The system
shall be capable of connection to a personal computer via RS 232
connection for monitoring and diagnostics. Firms responding to this
announcement must indicate whether they are a small, small
disadvantaged, and/or woman-owned business. Requests for solicitation
must be in writing or may be faxed to (407) 494-5560. The applicable
SIC code is 3679 and Small Business standard is 500. Requests for
solicitation must include telephone number, zip code. Please submit
request for solicitation by 20 Oct 95. (0278) Loren Data Corp. http://www.ld.com (SYN# 0161 19951006\61-0001.SOL)
61 - Electric Wire and Power and Distribution Equipment Index Page
|
|