|
COMMERCE BUSINESS DAILY ISSUE OF MAY 10,1995 PSA#1343NASA, John F. Kennedy Space Center, Kennedy Space Center, FL 32899 41 -- PAYLOAD CANNISTER ENVIRONMENTAL CONTROL SYSTEM POC Mario Baley,
McDonnell Douglas Space Systems, P. O. Box 21233, Kennedy Space
Center, FL 32815, 407-867-9321 ext. 5873. THIS IS NOT AN IFB OR RFP. NO
SOLICITATION EXISTS AND requests for a copy of a solicitation package
will not be considered. McDonnell Douglas Space & Defense Systems - KSC
is seeking to identify sources which can provide an Air Conditioning
Unit. Features are: 1. GENERAL: air cooling, heating, filtering,
dehumidifying unit, 100% outside air (or Recirculating type, optional).
Commercial grade, off-the-shelf, self-contained, trailer-mounted,
portable ground support equipment, within weatherproof enclosure for
outdoor use, with integral gasoline or diesel-powered generator. 2.
CAPACITY - COOLING: 50 degrees FDB coil leaving air temperature, and a
supply airflow of 1,000 CFM at 4 in. W.G. static pressure, minimum, at
outlet (for Recirculating type unit: 50 degrees FDB coil leaving air
temperature using 10% outside air, (return air: 86 degrees FDB, 74
degrees FWB) and a supply airflow of 1,500 CFM at 5 in. W.G. static
pressure, minimum, at outlet). HEATING/REHEATING: 16 kW (for
Recirculating type unit: 24 kW ). 3. DESIGN AMBIENT CONDITIONS: Summer:
96& FDB, 81& FWB, Winter: 20& FWB, 11& F dew point 4. Unit Enclosure:
weatherproof, corrosion resistant, painted, suitable for outdoor use in
humid coastal atmosphere, mounted on two-axle trailer, with ring tie
downs. 5. Refrigeration subsystem: refrigerant R-134a preferred, R-22
optional, industry standard-recognized components ( ARI, ASHRAE, ASME).
6) Air Distribution: Blower: industrial duty, non-sparking
construction, non-off gassing materials in airstream (also, compatible
with vapors of type J fluids, for Recirculating type unit). 7) Air
filters: 30% efficiency, charcoal (adsorption type), and 95%
efficiency. 8) Electrical equipment installation and controls: NFPA 70,
(also, class I, div. 2, group C & D for Recirculating type unit), NEMA
4 electrical enclosures, manual emergency shutdown. 9) Monitoring
capabilities (on display panel or stand-alone): air filter pressure
drop, supply air static pressure, supply airflow rate, evaporator coil
leaving air temperature, compressor suction pressure, compressor
discharge pressure, compressor suction temperature, compressor oil
temperature, compressor oil differential pressure. 10) Documentation:
operations and maintenance manual (electrical and mechanical
schematics, parts list, troubleshooting guide, maintenance procedures),
recommended spare parts list (for expected parts replacement within one
year). This synopsis is for planning purposes only, and does not
constitute a solicitation for bids or proposals and shall not be
construed as any commitment by McDonnell Douglas or the Government.
(0128) Loren Data Corp. http://www.ld.com (SYN# 0195 19950509\41-0004.SOL)
41 - Refrigeration, Air Condition and Air Circulating Equipment Index Page
|
|