J -- RFQ - BOILER REPAIR HUDSON VALLEY VAHCS - MONTROSE CAMPUS

Notice Date
8/25/2026 12:00:00 AM
 
Notice Type
Combined Synopsis/Solicitation
 
NAICS
238220 — Plumbing, Heating, and Air-Conditioning Contractors
 
Contracting Office
242-NETWORK CONTRACT OFFICE 02 (36C242) ALBANY NY 12208 USA
 
ZIP Code
12208
 
Solicitation Number
36C24226Q0816
 
Response Due
8/28/2026 7:00:00 AM
 
Archive Date
12/05/2026
 
Point of Contact
Natalie Acevedo, Contracting Officer, Phone: 718 584 9000 x4356
 
E-Mail Address
natalie.acevedo@va.gov
(natalie.acevedo@va.gov)
 
Small Business Set-Aside
SBA Small Business Set Aside - Total
 
Description
The purpose of this amendment to the solicitation is to: 1. Extend response due date to 8/31/2026 at 10:00 AM ET. 2. Respond to questions. RFI 6 - Master Control Panel and SCADA Integration The propane header must interface with the existing Master Control Panel and SCADA system. During the walkthrough, MicroMod advised that the existing Master Control Panel has insufficient available I/O for the propane-system interface. MicroMod further advised that an upgraded Red Lion platform could be configured with the additional I/O and communications capability required for this integration. Requested VA Response: Please confirm whether the contract scope includes all required I/O hardware, Red Lion HMI or communications-platform upgrades, programming, graphics, and Master Control Panel/SCADA modifications necessary to provide a complete and operational propane-system interface. VA Response: � Contractor shall furnish and install an electro mechanical gas shut off valve (Maxon or approved equal)� upstream of the fuel pressure regulator� and� downstream of the gas filter/strainer� to protect the downstream safety shut off valves.� The VA will provide at least one additional I/O module in the Boiler Plant Master control panel which will control the propane gas shut off valve. The contractor shall furnish and install the 110V power circuit from the I/O module to the propane gas shut off valve. The VA will provide the additional I/O prior to the completion of the contract work. RFI 7 - Boiler No. 2 Human-Machine Interface During the recent walkthrough, it was observed that the Boiler No. 2 control cabinet no longer has a functional Human-Machine Interface (HMI). A working HMI is required to interface with the existing MicroMod loop controllers and to configure, monitor, start up, test, and commission the Boiler No. 2 combustion-control system. A direct hardware swap is not adequate because current Red Lion models do not duplicate the obsolete unit's side-button arrangement; the existing screens and graphics must be re-engineered and converted for the new display. Requested VA Response: Please confirm whether the contract scope will be revised to include furnishing, engineering, programming, graphics conversion, installation, integration, testing, and commissioning of a new Red Lion HMI compatible with the existing MicroMod loop controllers and associated boiler-control equipment. Supporting Information: See Attachment E - Boiler No. 2 HMI Replacement. VA Response: The VA will have a new HMI installed prior to the completion of the contract work.
 
Web Link
SAM.gov Permalink
(https://sam.gov/workspace/contract/opp/181c85ef0c8d442d8d70449c97d4fdb2/view)
 
Place of Performance
Address: Hudson Valley VA Healthcare System Montrose Campus 2094 Albany Post Road, Montrose, NY 10548-1454, USA
Zip Code: 10548-1454
Country: USA
 
Record
SN07941927-F 20260827/260825230042 (samdaily.us)
 
Source
SAM.gov Link to This Notice
(may not be valid after Archive Date)

| FSG Index  |  This Issue's Index  |  Today's SAM Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers
 Privacy Policy  Jenny in Wanderland!  © 1994-2026, Loren Data Corp.