Loren Data's SAM Daily™

fbodaily.com
Home Today's SAM Search Archives Numbered Notes CBD Archives Subscribe
SAMDAILY.US - ISSUE OF SEPTEMBER 14, 2025 SAM #8693
SOLICITATION NOTICE

Z -- Backflow, valves and chiller replacements

Notice Date
9/12/2025 7:06:51 AM
 
Notice Type
Solicitation
 
NAICS
238220 — Plumbing, Heating, and Air-Conditioning Contractors
 
Contracting Office
ATF WASHINGTON DC 20226 USA
 
ZIP Code
20226
 
Solicitation Number
15A00025Q00000111
 
Response Due
9/16/2025 12:00:00 PM
 
Archive Date
10/01/2025
 
Point of Contact
Brandon Hodnett
 
E-Mail Address
Brandon.Hodnett@atf.gov
(Brandon.Hodnett@atf.gov)
 
Small Business Set-Aside
SBA Total Small Business Set-Aside (FAR 19.5)
 
Description
The Contractor shall furnish all equipment, materials, and labor required to perform the following 3 mechanical services: Backflow Preventors Supply and install 2 each 8� Zurn/Wilkins or equivalent BFP Supply and install 1 each 4� Zurn/Wilkins or equivalent BFP Supply and install 1 each 1.5� Zurn/Wilkins or equivalent BFP Main Gate Valves Supply and install two 8"" valves on the effluent side of the backflow preventers. Replace two 8"" flanged ductile 90's, one 8"" tee, and the seven bolt & gasket kits. NOTE-This work will need to be completed during off hours. Chiller Pipe Replacement Replace the IO-inch schedule 40-weld pipe (up to 8 feet) that is leaking in the ceiling of the chiller room. Remove the section of IO-inch schedule 40 weld pipe (up to 8 feet) Tis will require disconnecting the chemical feed line. Install 2 new thread-o-lets, plug one off and connect the new chemical line. Replace the schedule 80 PVC all the way back to the ball valve with new split rings. Leak checked to be performed and monitored by building engineers for 24 hours before insulating Install new insulation and wrapping over new pipe and tie into existing. The plastic vinyl 90's may be reused if not damaged during removal The contractor shall provide and use a smoke eater during all welding, grinding, cutting, and torching of the pipe. Provide necessary fire safety equipment and inform building engineers when fire or sparks will be taking place.
 
Web Link
SAM.gov Permalink
(https://sam.gov/workspace/contract/opp/dcf24ed559c8412393a7d32c6c20eef9/view)
 
Place of Performance
Address: Beltsville, MD 20705, USA
Zip Code: 20705
Country: USA
 
Record
SN07589024-F 20250914/250912230043 (samdaily.us)
 
Source
SAM.gov Link to This Notice
(may not be valid after Archive Date)

FSG Index  |  This Issue's Index  |  Today's SAM Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers
 Privacy Policy  Jenny in Wanderland!  © 1994-2024, Loren Data Corp.