SOLICITATION NOTICE
Z -- 537-19-124 Upgrade Nurse Call
- Notice Date
- 2/21/2022 10:35:49 AM
- Notice Type
- Solicitation
- NAICS
- 238210
— Electrical Contractors and Other Wiring Installation Contractors
- Contracting Office
- 252-NETWORK CONTRACT OFFICE 12 (36C252) MILWAUKEE WI 53214 USA
- ZIP Code
- 53214
- Solicitation Number
- 36C25222B0012
- Response Due
- 2/24/2022 7:00:00 AM
- Archive Date
- 03/26/2022
- Point of Contact
- Ryan J McMillin, Contracting Officer
- E-Mail Address
-
Ryan.McMillin@va.gov
(Ryan.McMillin@va.gov)
- Awardee
- null
- Description
- Question 1: The RFI #3 below state that only conduit in Bldg. 40 can be reused. Every electrical drawing notes The DEISGN INTENT is to re-use the existing raceway where new devices are replacing devices in the same location. See the demo drawings for reference. Can this question be clarified further? Do can conduit be reused in all buildings as shown on the drawings? Answer: Conduit cannot be reused in all buildings; only conduit in Bldg. 40 can be reused as described in RFI #3 response. Question 2: There are conflicting notes in regards to the rough-in system for the low voltage systems. Is full conduit required even in accessible ceilings? Or is free air acceptable? Answer: Cabling can be run across j-hooks within accessible corridor ceiling spaces only. Contractor must submit coordination drawings showing proposed raceway system and run across j-hooks for VA review prior to installation.
- Web Link
-
SAM.gov Permalink
(https://sam.gov/opp/ab93b59c7f0f4dd2ae27eaa1ba05ab06/view)
- Record
- SN06247788-F 20220223/220221230102 (samdaily.us)
- Source
-
SAM.gov Link to This Notice
(may not be valid after Archive Date)
| FSG Index | This Issue's Index | Today's SAM Daily Index Page |