Loren Data's SAM Daily™

fbodaily.com
Home Today's SAM Search Archives Numbered Notes CBD Archives Subscribe
SAMDAILY.US - ISSUE OF JUNE 19, 2020 SAM #6777
SOURCES SOUGHT

H -- Load Bank Testing Services Eastern Oklahoma VA Health Care System Muskogee Ok 74401

Notice Date
6/17/2020 8:56:37 AM
 
Notice Type
Sources Sought
 
NAICS
811219 — Other Electronic and Precision Equipment Repair and Maintenance
 
Contracting Office
NETWORK CONTRACT OFFICE 19 (36C259) Greenwood Village CO 80111 USA
 
ZIP Code
80111
 
Solicitation Number
36C25920Q0460
 
Response Due
6/24/2020 3:00:00 PM
 
Archive Date
09/22/2020
 
Point of Contact
Lance Davis, Contract Specialist, Phone: 918-577-3838
 
E-Mail Address
Lance.Davis2@va.gov
(Lance.Davis2@va.gov)
 
Awardee
null
 
Description
Load Bank Testing Service VA Eastern Oklahoma Health Care System VA Medical Center Muskogee, OK. 74401 BRIEF SCOPE OF WORK (This is for information only) Load Bank Testing Services of 7 Emergency Generators in accordance with the terms and conditions stated within this abbreviated Performance Work Statement (PWS). This is a Request for Information (RFI) Only for Market Research purposes, no Award will be made from this RFI. The subsequent Contract will be a Base with Four possible Option Year(s) Contract, funded by FY21 appropriations, with a start date on or after 1 October 2020. Introduction: This Statement of Work (SOW) describes the requirements for the Load Bank testing of 7 Emergency Generators. VA will supply transformer for testing of the 1250KW Generator. This SOW describes the requirements for the Qualified Generator installation, repair, and testing company, Contract Professionals known as Contractors in this document, hereafter. Contractors who are contracted by the Jack C. Montgomery VA Medical Center to perform work, and all of its components shall meet all requirements stated in Section 2 of this SOW. 2. Qualifications of Contractors: Contractors shall be certified Generator Installation, Repair, and Testing, and completed the Occupational Safety & Health Administration (OSHA) approved 10-hour construction safety training or certification by contactor of OSHA training. Documented when arrival on station to COR Contractors shall have technical trainings, and track records of working experience in maintenance, inspection, and repairing Generators and its components in healthcare, industrial, educational, and commercial facilities for a minimum of five (5) continuous years. Documented and submitted with bid. Contractors shall have safety trainings either on-the-job or class-room type - in electrical safety outlined in the OSHA Standard 29 Code of Federal Regulations (CFR) 1910 Subpart S Electrical, and the NFPA 70E Standard for Electrical Safety in the Workplace. Training certifications shall be submitted to the VA Contracting Officer prior to work. If no training certifications are available, the contractor Employer shall certify that he/she has met this requirement in writing and submit it to the VA Contracting Officer prior to work. Contractors shall have ready access to the latest versions of the following references: NFPA 70, National Electrical Code. NFPA 70B, Recommended Practice for Electrical Equipment Maintenance. NFPA 70E, Standard for Electrical Safety for the Workplace. OSHA Standard 29 CFR 1910, Subparts I & S. NFPA 110, Generators Documented when arrival on station to COR Contractors shall be equipped with all necessary tools, equipment, and Personal Protective Equipment (PPE) to perform the work safely, effectively, and timely. Tools, equipment, and PPE shall comply with the requirements of OSHA Standard 29 CFR 1910, Subpart I, and NFPA 70E. Documented when arrival on station to COR. 3. Summary of Work/ Performance Measures: Contractor shall be responsible for any necessary repairs (mechanical and/or electrical) to complete the required load bank testing. Contractor shall provide all travel and equipment to complete Load Bank testing as described in NFPA 110; 8.4.2.3 and VHA Directive 2006-056. During monthly test of diesel powered generators, if load is not at 30% of name plate rating of generator it shall be exercised annually. (Generators that need to be Load bank tested are identified in section D). The load bank testing described below in section B will be the required four (4) hour test for FY years 2022 & 2025. Load Banking shall be done with supplemental loads at 25% name plate rating for 60 minutes, followed by 50% of name plate rating for 60 minutes, followed by 75% of name plate rating for 60 minutes, followed by 100% rating for 60 minutes for a total of 4 continuous hours. (Ref. NFPA 110 section 8.4.2.3.) This portion of the testing is only performed every third year with FY 2022 and FY 2025 being the years for the 4-hour load bank test. Contractor shall be responsible for any necessary repairs (mechanical and/or electrical) to complete the required load bank testing. Contractor shall provide all travel and equipment to complete Load Bank testing as described in NFPA 110; 8.4.2.3 and VHA Directive 2006-056. During monthly test of diesel powered generators, if load is not at 30% of name plate rating of generator it shall be exercised annually. (Generators that need to be Load bank tested are identified in section D). The load bank testing described in section D will be the required two (2) hour test for FY years 2021 & 2023 & 2024. Load Banking shall be done with supplemental loads at 25% name plate rating for 30 minutes, followed by 50% of name plate rating for 30 minutes, followed by 75% of name plate rating for 60 minutes, for a total of 2 continuous hours. (Ref. NFPA 110 section 8.4.2.3.) Scheduling of testing will be through the VA s Electrical Supervisor Luke Roberts at 918-577-4493. Scheduling may be day, evening, or weekend. Depending upon the VA Medical Centers patient care needs. Testing will be strictly at the Medical Centers convenience. Testing for the generators serving the Surgery suite will be scheduled when Surgery is not performing Surgeries. All load bank testing will be scheduled for the month of May. The Medical Center has 7 generators that do not meet the 30% and must have supplemental load band testing completed. Generator Name EE# KW Rating Average Load Area served by generator Fuel tank #56 Unit#1 16021 750 KW 900 A 480 V 280 AMP 30% Buildings #52 & 53, Chiller Plant and In-patient Care 10,000 gal. #56 Unit#2 16022 750 KW 900 A 480 V 249 AMP 27% Buildings #52 & 53, Chiller Plant and In-patient Care Shared with unit #1 #46A 35171 350 KW 970 A 208 V 180 AMP 23% Buildings #1, #22, and #24, Out-patient clinics, Nutrition Food Service, Main Computers, and Offices. It is tied to Generator #46B with paralleling switch. 2,000 gal #46B 35170 350 KW 970 A 208 V 150 AMP 15% Buildings #1, #22, and #24, Out-patient clinics, Nutrition Food Service, Main Computers, and Offices. It is tied to Generator #46B with paralleling switch. Shared with Generator #46A #18 26567 250 KW 693 A 208 V 110 AMP 15 % Buildings #11, 18, and 54, Engineering, Boiler Plant, and High Voltage Switchgear building. 1,000 gal #8 175 KW 700 A 240 V Single phase Buildings 6,7,8,9,10 900 gal # 52 36248 74 A 1280KW 12470V ?? Bldg. 52 Chiller Plant 1500 Contractor shall submit a report containing any malfunctions or problems identified during testing with recommendations for repairs. Location of performance VA Eastern Oklahoma Health Care System VA Medical Center 1011 Honor Heights Drive Muskogee OK 74401 IMPORTANTR NOTE: This RFI (Request for Information) is for information only. No award will be made from this RFI. Please communicate via e-mail to Lance.Davis2@va.gov by COB June 24, 2020 as to your company s ability to perform service per this brief Scope of Work. If interested, please provide the following: Please state your company s business size Please provide DUNS number If you have a FSS/GSA contract that includes this service Provide FSS/GSA contract number if applicable
 
Web Link
SAM.gov Permalink
(https://beta.sam.gov/opp/0cad3efac1c0479494f8469b6af97d35/view)
 
Place of Performance
Address: Eastern Oklahoma VA Health Care System VA Medical Center 1011 Honor Heights Drive, Muskogee, OK 74401, USA
Zip Code: 74401
Country: USA
 
Record
SN05694736-F 20200619/200617230200 (samdaily.us)
 
Source
SAM.gov Link to This Notice
(may not be valid after Archive Date)