SOLICITATION NOTICE
H -- Service -Emergency/Backup Generator Semi-Annual Preventative Maintenance and Annual Load Bank Testing. Fort Meade/Hot Springs VAMC Campuses, South Dakota
- Notice Date
- 5/15/2019
- Notice Type
- Combine Synopsis/Solicitation
- NAICS
- 811310
— Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance
- Contracting Office
- Department of Veterans Affairs;Network 23 Contracting Office (NCO 23);113 Comanche Rd.;Fort Meade SD 57741
- ZIP Code
- 57741
- Solicitation Number
- 36C26319Q0193
- Response Due
- 6/3/2019
- Archive Date
- 8/2/2019
- Point of Contact
- David A. Raad, david.raad@va.gov
- Small Business Set-Aside
- Total Small Business
- Description
- SCOPE OF WORK Semi-Annual VA BHHCS Emergency Generator Testing and Maintenance Provide semi-annual preventive maintenance inspections and services on emergency generators at the VA medical Centers at Ft Meade and Hot Springs, South Dakota. Inspection reports from attachments A & B to be provide to facilities POC s. Contract POC s for scheduling work and coordination are as follows: Fort Meade VAMC: CJ Bradley Operations Supervisor, Phone: 605-720-7134 Hot Springs VAMC: Dan Cerveny, Maintenance Supervisor, Phone 605-745-2268 Fort Meade Emergency Generator equipment included in the scope of work is as follows: Bldg. 113 Emergency Generator Manufacturer: Cummins / 750 KW Generator Model; DQCB-1641706 / Serial Number: K160128689 Engine Model: QSK23G7 / Serial Number: 85002334 Bldg. 148 Emergency Generator Manufacturer: Cummins / Onan / 125 KW Generator Model: DSGAB- 1321187 / Serial Number: B130456361 Engine Model: QSB7 G5 NR3 / Serial Number: 73494119 Bldg. 145 Emergency Generator Manufacturer: Cummins/ 250 KW Generator Model: DQDAA-1660802 / Serial Number: L160128689 Engine Model: QSL9-G7 / Serial Number: 74068824 Bldg. 137 Emergency Generator Manufacturer: Cummins / Onan / 100 KW Generator Model: DSGAA- 1321189 / Serial Number: B130456362 Engine Model: QSB7 G5 NR3 / Serial Number: 73493506 Bldg. 160 Emergency Generator Manufacturer: DMH/ 165 KW Generator Model: 200CL3 / Serial Number: 94-45-74-1 Engine Model: LTA-1062/ Serial Number: 34737406 Bldg. 155 Main Station Generator Manufacturer: Marathon / 2000KW Generator Model: 1020FDH1242 / Serial Number: WA-6003864-0717 Engine Model: CD2000SX6T2 / Serial Number: 179811-1-1-1108 Bldg. T296 Fire Station Emergency Generator Manufacturer: Cummins / Onan / 49HP Generator Model; DSKCA-193329 / Serial Number: L090070761 3. Hot Springs VAMC Emergency Generator equipment included in the scope of work is as follows: Bldg. 10 Emergency Generator Manufacturer: Generac Generator Model: 98A03219-S/ Serial Number: 2042251 Engine Model: 92460 / Serial Number: G3407-2 Bldg. 12 Emergency Generator Manufacturer: Generac Generator Model: 433RSL4021/ Serial Number: LM-239579-0701 Engine Model: OA8829/ Serial Number: 8DC9-446846 Bldg. 18 Emergency Generator Manufacturer: Onan Generator Model: 230DFAB / Serial Number: A980673745 Engine Model: LTA10-G1 / Serial Number: 12079 Mobile MRI Emergency Generator Manufacturer: John Deere Generator Model: 4045hf285H,I,J / Serial Number: PE4045L250238 Mobile CT Emergency Generator Manufacturer: John Deere Generator Model: 4045 Bld. 66 Emergency Generator Manufacture: Cummins Generator Model 125 DSGAB Engine Model: QSB7-G5 NR3 Semi-annual Inspections will be completed in August/September and March/April and inspection reports are to be provided to the VAMC POC s within 30 days of completion of work. Work shall be scheduled 7 days in advance of planned work to minimize disruption to the facility. The Scope of September/October inspections and testing will include all work outlined in Attachment A. The scope of March/April Inspections will include all work outlined in Attachment B. Annual Load Bank Testing included in Attachment A will be accomplished in accordance with NFPA 110 (99) Sec 6-4.2.2. Publication 2013. The testing shall be documented and supplemental loads included at 25% of the name plate rating for 30 minutes followed by 50 percent of the nameplate rating for 30 minutes, followed by 75 percent. All emergency generators will be load bank tested annually unless otherwise noted for specific generator listed above. NOTE: THIS NOTICE WAS NOT POSTED TO FEDBIZOPPS ON THE DATE INDICATED IN THE NOTICE ITSELF (15-MAY-2019); HOWEVER, IT DID APPEAR IN THE FEDBIZOPPS FTP FEED ON THIS DATE. PLEASE CONTACT 877-472-3779 or fbo.support@gsa.gov REGARDING THIS ISSUE.
- Web Link
-
Link To Document
(https://www.fbo.gov/spg/VA/VABHHCS568/VABHHCS568/36C26319Q0193/listing.html)
- Place of Performance
- Address: Department of Veterans Affairs;VAMC FORT MEADE & HOT SPRINGS;113 Comanche Rd.;Fort Meade SD
- Zip Code: 57741
- Country: USA