MODIFICATION
61 -- Isolation Transformer Rental for San Diego, CA - 1/13/16 - Amendment 1
- Notice Date
- 12/22/2015
- Notice Type
- Modification/Amendment
- NAICS
- 335311
— Power, Distribution, and Specialty Transformer Manufacturing
- Contracting Office
- Department of the Navy, Naval Sea Systems Command, Portsmouth Navy Shipyard, Building 170, Kittery, Maine, 03904-5000, United States
- ZIP Code
- 03904-5000
- Solicitation Number
- N39040-16-T-0052
- Archive Date
- 1/31/2017
- Point of Contact
- Emily Bateman, Phone: 2074386819
- E-Mail Address
-
emily.bateman@navy.mil
(emily.bateman@navy.mil)
- Small Business Set-Aside
- N/A
- Description
- N39040-16-T-0052-0001 Amendment ********************************** Q1: Regarding X05, are you feeding the disconnect with 6 separate breakers then out to 6 other breakers? A1: The breaker will be fed by (6) individual 400A circuits, and then feed into the X04 Switchboard with 3(+1 spare) 800A breakers. This will allow large power demands requiring over 400A to be powered without having to feed the same unit with two separate breakers. **********************************
- Web Link
-
FBO.gov Permalink
(https://www.fbo.gov/notices/8ac010ea28348aaa07bf40850dc4daa0)
- Place of Performance
- Address: San Diego, California, United States
- Record
- SN03976025-W 20151224/151222234355-8ac010ea28348aaa07bf40850dc4daa0 (fbodaily.com)
- Source
-
FedBizOpps Link to This Notice
(may not be valid after Archive Date)
| FSG Index | This Issue's Index | Today's FBO Daily Index Page |