61 -- Isolation Transformer Rental for San Diego, CA - 1/13/16 - Amendment 1

Notice Date
12/22/2015
 
Notice Type
Modification/Amendment
 
NAICS
335311 — Power, Distribution, and Specialty Transformer Manufacturing
 
Contracting Office
Department of the Navy, Naval Sea Systems Command, Portsmouth Navy Shipyard, Building 170, Kittery, Maine, 03904-5000, United States
 
ZIP Code
03904-5000
 
Solicitation Number
N39040-16-T-0052
 
Archive Date
1/31/2017
 
Point of Contact
Emily Bateman, Phone: 2074386819
 
E-Mail Address
emily.bateman@navy.mil
(emily.bateman@navy.mil)
 
Small Business Set-Aside
N/A
 
Description
N39040-16-T-0052-0001 Amendment ********************************** Q1: Regarding X05, are you feeding the disconnect with 6 separate breakers then out to 6 other breakers? A1: The breaker will be fed by (6) individual 400A circuits, and then feed into the X04 Switchboard with 3(+1 spare) 800A breakers. This will allow large power demands requiring over 400A to be powered without having to feed the same unit with two separate breakers. **********************************
 
Web Link
FBO.gov Permalink
(https://www.fbo.gov/notices/8ac010ea28348aaa07bf40850dc4daa0)
 
Place of Performance
Address: San Diego, California, United States
 
Record
SN03976025-W 20151224/151222234355-8ac010ea28348aaa07bf40850dc4daa0 (fbodaily.com)
 
Source
FedBizOpps Link to This Notice
(may not be valid after Archive Date)

FSG Index  |  This Issue's Index  |  Today's FBO Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers
 Privacy Policy  Jenny in Wanderland!  © 1994-2024, Loren Data Corp.