SOURCES SOUGHT
59 -- AC-DC Power Supply
- Notice Date
- 12/10/2015
- Notice Type
- Sources Sought
- NAICS
- 334419
— Other Electronic Component Manufacturing
- Contracting Office
- Department of Energy, Fermi National Accelerator Laboratory, Fermilab, P.O. BOX 500, MAIL STOP 210 (WH4W), BATAVIA, Illinois, 60510
- ZIP Code
- 60510
- Solicitation Number
- 260748-MJG
- Archive Date
- 12/15/2015
- Point of Contact
- Mark J. Graczyk, Phone: 6308404895, ,
- E-Mail Address
-
markgrac@fnal.gov,
(markgrac@fnal.gov, /div)
- Small Business Set-Aside
- N/A
- Description
- 1 UNIT DELIVERY BY END OF jANUARY 2016 Inflector power supply specification, version 4c Input Power: 480 VAC, 3 phase, 60 Hz. Power Factor: 0.9 or better at full output current. DC Output: 0 to 5 Volts DC at 3600 Amps continuous. Output Current Ripple: Less than 0.1% peak to peak of rated DC output current with a 2.0 mH load. Regulation: Internal constant voltage mode: -less than +-0.1%total envelope of uncertainty. -recovery to +-0.5% within 50 mSec following a line voltage step of +-10%. -overshoot and undershoot of programmed output less than 2% with a recovery in 100 mSec. Internal constant current mode: -less than +-0.1%total envelope of uncertainty. -stability better than +-0.1% for 8 hours after one hour warm up. -stable operation of the power supply in constant current mode is required for a load of 150 microOhms and 2 milliHenry. Isolation: AC Input: +-2000 volts to ground. DC output: +-1000 volts to ground. Control I/O: referenced to local earth ground. Control I/O: -Analog inputs for programming capability for constant current or constant voltage modes. -External Interlock Input, closed contact required for P.S. run or enabled function, fast shutdown or clamp capability would be desirable here. -Buffered analog readouts for output current and output voltage monitoring. -Standard RS232 remote control functions. -TCP/IP Ethernet remote control. -Front panel readouts of output current and voltage. -Front panel readouts of interlock status. -Front panel controls for local current and voltage settings, DC on, DC off, and interlock reset. Internal Interlocks: Power supply will be protected from: -DC output over-voltage. -DC output over-current. -AC input imbalance if pre-regulator is used. -Internal over-temperature of semiconductors, power magnetics, and DC bus work. -Lack of or insufficient cooling water. Physical Specifications: -Maximum Footprint: approx. 24" wide by 32" deep. -The equipment cabinet will be equipped with lockable casters. -The power supply shall be water cooled. Misc: -480 VAC input power connections shall be covered for personnel protection. -Input AC power over current protection for the input 480 VAC, if provided with the power supply, shall be protected from accidental operation. -Optional power supply free wheeling diode rated for full output current or greater of power supply for minimum of 2 minutes. -Documentation in the form of a user manual by manufacturer.
- Web Link
-
FBO.gov Permalink
(https://www.fbo.gov/spg/DOE/FERMI/FERMI/260748-MJG/listing.html)
- Place of Performance
- Address: FERMI NATIONAL ACCELERATOR LABORATORY, KIRK AND PINE ST, BATAVIA, Illinois, 60510, United States
- Zip Code: 60510
- Zip Code: 60510
- Record
- SN03966234-W 20151212/151210234315-f9a8b35cf3d98148c33e36afe3c8f21d (fbodaily.com)