G -- Provide semi-annual preventive maintenance inspections and services and annual load bank testing on emergency generators - Attachment

Notice Date
4/10/2015
 
Notice Type
Attachment
 
NAICS
335311 — Power, Distribution, and Specialty Transformer Manufacturing
 
Contracting Office
Department of Veterans Affairs;VA Black Hills HCS;Fort Meade Campus;113 Comanche Rd.;Fort Meade SD 57741
 
ZIP Code
57741
 
Solicitation Number
VA26315Q0550
 
Response Due
4/17/2015
 
Archive Date
5/17/2015
 
Point of Contact
Philip Flinders
 
Small Business Set-Aside
N/A
 
Description
Statement of Work Annual Service Maintenance Emergency Generators BHHCS 1.Provide semi-annual preventive maintenance inspections and services on emergency generators at the VA medical Centers at Ft Meade and Hot Springs, South Dakota. Inspection reports from attachments A & B to be provide to facilities POC's. 2.Contract POC's for scheduling work and coordination are as follows: Fort Meade VAMC: Tom Smith, Operations Supervisor, Phone: 605-720-7134 Hot Springs VAMC: Dan Cerveny, Maintenance Supervisor, Phone 605-745-2268 3.Fort Meade Emergency Generator equipment included in the scope of work is as follows: A.Bldg. 113 Emergency Generator - Manufacturer: John Deere / KatoLight / 350 KW Generator Model; 433PSL6216 / Serial Number: WA-547830-1205 Engine Model: D350FPJ4 / Serial Number: 119198-0106 B.Bldg. 148 Emergency Generator - Manufacturer: Cummins / Onan / 125 KW Generator Model: DSGAB- 1321187 / Serial Number: B130456361 Engine Model: QSB7 - G5 NR3 / Serial Number: 73494119 C.Bldg. 145 Emergency Generator - Manufacturer: Caterpillar / KatoLight / 230 KW Generator Model: SR4B / Serial Number: 6YR02788 Engine Model: 3306 / Serial Number: 9NR05844 D.Bldg. 137 Emergency Generator - Manufacturer: Cummins / Onan / 100 KW Generator Model: DSGAA- 1321189 / Serial Number: B130456362 Engine Model: QSB7 - G5 NR3 / Serial Number: 73493506 E.Bldg. 160 Emergency Generator - Manufacturer: Cummins /Onan / 165 KW Generator Model: UC1274H / Serial Number: F940545538 F.Bldg. 155 Main Station Generator - Manufacturer: Detroit / KatoLight / 2000KW Generator Model: 744SFM4988 / Serial Number: WA567823-0908 Engine Model: CD2000SX6T2 / Serial Number: 79811-1-1-1208 G.Bldg. T296 Fire Station Emergency Generator - Manufacturer: Cummins / Onan / 49HP Generator Model; DSKCA-193329 / Serial Number: L090070761 3. Hot Springs VAMC Emergency Generator equipment included in the scope of work is as follows: A.Bldg. 10 Emergency Generator - Manufacturer: Generac Generator Model: 98A03219-S/ Serial Number: 2042251 Engine Model: 92460 / Serial Number: G3407-2 B.Bldg. 12 Emergency Generator - Manufacturer: Generac Generator Model: 433RSL4021/ Serial Number: LM-239579-0701 Engine Model: OA8829/ Serial Number: 8DC9-446846 C.Bldg. 18 Emergency Generator - Manufacturer: Onan Generator Model: 230DFAB / Serial Number: A980673745 Engine Model: LTA10-G1 / Serial Number: 12079 D.Mobile MRI Emergency Generator - Manufacturer: John Deere Generator Model: 4045hf285H,I,J / Serial Number: PE4045L250238 E.Mobile CT Emergency Generator - Manufacturer: John Deere Generator Model: 4045 4.Semi-annual Inspections will be completed in August/September and March/April and inspection reports are to be provided to the VAMC POC's within 30 days of completion of work. Work shall be scheduled 7 days in advance of planned work to minimize disruption to the facility. 5.The Scope of August/September inspections and testing will include all work outlined in Attachment A. The scope of March/April Inspections will include all work outlined in Attachment B. 6. Annual Load Bank Testing included in Attachment A will be accomplished in accordance with NFPA 110 (99) Sec 6-4.2.2. The testing shall be documented and supplemental loads included at 25% of the name plate rating for 30 minutes followed by 50 percent of the nameplate rating for 30 minutes, followed by 75 percent All emergency generators will be load bank tested with exception of the following generators: Fort Meade: Bldg. 155 Main Station Generator, Bldg. T296 Fire Station Emergency Generator Hot Springs: Mobile MRI Emergency Generator, Mobile CT Emergency Generator 1.0
 
Web Link
FBO.gov Permalink
(https://www.fbo.gov/spg/VA/VABHHCS568/VABHHCS568/VA26315Q0550/listing.html)
 
Document(s)
Attachment
 
File Name: VA263-15-Q-0550 VA263-15-Q-0550.docx (https://www.vendorportal.ecms.va.gov/FBODocumentServer/DocumentServer.aspx?DocumentId=1975457&FileName=VA263-15-Q-0550-003.docx)
Link: https://www.vendorportal.ecms.va.gov/FBODocumentServer/DocumentServer.aspx?DocumentId=1975457&FileName=VA263-15-Q-0550-003.docx

 
Note: If links are broken, refer to Point of Contact above or contact the FBO Help Desk at 877-472-3779.
 
Place of Performance
Address: BHHCS;Fort Meade & Hot Springs;113 Comanche St.;Fort Meade, SD
Zip Code: 55417
 
Record
SN03696158-W 20150412/150410234549-936ceddf0138fb3d83f4fc83484b6f92 (fbodaily.com)
 
Source
FedBizOpps Link to This Notice
(may not be valid after Archive Date)

FSG Index  |  This Issue's Index  |  Today's FBO Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers
 Privacy Policy  Jenny in Wanderland!  © 1994-2024, Loren Data Corp.