- QUESTIONS AND ANSWERS; Question 1: For the coating repair work you do not specify any painting system to be used for the coating repairs. Answer 1: ***Use AWWA Standard D102, Coating Steel Water Storage Tanks/ANSI/NSF Standard 61 Contractor shall furnish one of the proprietary systems equal to the Tnemec Company, Inc systems or a prior Government Approved system: Primer Coat - Tnemec Series 94-H2O Hydro-Zinc applied to a dry film thickness of 2.5 - 3.5 dry mils. Thin only with approved thinner, tnemec 41-3 or 41-49 thinner. Stripe Coat - All vertical/horizontal seams, ceiling overlapping plate edge, ceiling support beams, support columns, ceiling to shell joint, nuts, bolts, ladders, pits, and all other irregular surfaces shall receive on coat of Tnemec Series FC20HS-1255 Beige Pota-Pox applied to a dry film thickness of 2.0-3.0 dry mils. Application shall be spray and back brush and/or rolled. Applied coating shall not be recoated until minimum recoating time has been satisfied as per manufacturer's recommendations. Finish Coat - Tnemec Series 141 Epoxoline applied to a dry film thickness of 10.0-12.0 dry mils. Thin only with approved thinner, Tnemec 41-4 thinner. Question 2: For the coating repair work you do not specify any surface preparation, do you want the areas to be repaired blasted? Answer 2: All interior surfaces shall be prepared in accordance with Steel Structures Painting Council SSPC-SPC10 "Near White Blast Cleaning", with a minimum 2.0 mil angular surface profile. Steel shall be thoroughly cleaned of rust, mill scale, dirt and all other foreign substances. Question 3: You request the float to be coated, will the float be removed from the tank? Answer 3: There will be nothing removed by the government, contractor to perform all work. Preference would be to minimize cost and downtime of tank, but contractor may have to make a decision upon physical inspection.
- Web Link
-
FBO.gov Permalink
(https://www.fbo.gov/notices/2b3a8e7571f07324569ecc28a541ff1c)
- Place of Performance
- Address: Barskdale AFB, LA, Barksdale AFB, Louisiana, 71110, United States
- Zip Code: 71110
- Record
- SN03312710-W 20140319/140317234654-2b3a8e7571f07324569ecc28a541ff1c (fbodaily.com)
- Source
-
FedBizOpps Link to This Notice
(may not be valid after Archive Date)
| FSG Index | This Issue's Index | Today's FBO Daily Index Page |