Loren Data's SAM Daily™

fbodaily.com
Home Today's SAM Search Archives Numbered Notes CBD Archives Subscribe
FBO DAILY ISSUE OF SEPTEMBER 20, 2012 FBO #3953
MODIFICATION

66 -- Contractor shall provide all equipment, material, services, and labor to furnish and install a new Continuous Emissions Monitoring Systems(CEMS) for two Medical/Infectious Waste Incinerators located at the DPW, Fort Detrick MD 21702

Notice Date
9/18/2012
 
Notice Type
Modification/Amendment
 
NAICS
334513 — Instruments and Related Products Manufacturing for Measuring, Displaying, and Controlling Industrial Process Variables
 
Contracting Office
US Army Medical Research Acquisition Activity, ATTN: MCMR-AAA, 820 Chandler Street, Frederick, MD 21702-5014
 
ZIP Code
21702-5014
 
Solicitation Number
W81XWH12R0065
 
Response Due
9/20/2012
 
Archive Date
11/19/2012
 
Point of Contact
carl.gorkos, 3016192110
 
E-Mail Address
US Army Medical Research Acquisition Activity
(carl.gorkos@amedd.army.mil)
 
Small Business Set-Aside
Total Small Business
 
Description
NO further questions will be accepted. This is the last response. 24. Question: What is the I/O count for each unit? 24A. Answer: There are 24 I/O switches on each unit, for a total of 48 I/O switches. 24. What is the I/O count for each unit? 24A. There are 24 I/O switches on each unit, for a total of 48 I/O switches. 25.Based on the technical responses per the amendment, it is clear that a transformer will not be required. Two of the four breakers from the existing power distribution panel are double pole 60A breakers. Since our CEMS requires 120 VAC power, I would assume the double pole (208 VAC) breakers could be replaced with single pole 120 VAC breakers? 25A. Yes. The panel is a "Square D" type with snap in breakers 26.In section 2.1.5: It states the data acquisition needs to be an integral part of the analyzer system either in conjunction with the analyzer/sample conditioning cabinet or in a separate cabinet. Would a triple-bay NEMA-12 cabinet (unibody type) configuration be acceptable instead of 3 separate NEMA-12 single bay cabinets? The triple-bay would have 3 each front and 3 each rear doors with no interior walls for cooling circulation. The approximate footprint is 75"W x 32"D which is within the size of your concrete pad. 26A. As long as each Continuous Emission Monitoring system can be configured to stand alone, independent of the other, then the relative placement, whether all in one enclosure or each with their own is not an issue. Enclosures must be simple to open and easy to access, if the question suggests that analyzers, sample conditioners and pumps would be placed in a cabinet at ground level so that access would be impeded then the answer is this cannot be allowed. 27.Section 2.1.5.a: Is a UPS only required for the DAS? Do each of the CEMS require a UPS as well as the DAS? 27A. The system that is detailed in this specification, is a duplicate of the existing. Only one UPS exists for the DAS. 28.Section 2.1.4: This section states that the vendor shall supply calibration gases sufficient to calibrate at least two (2) points in the range of each analytical instrument. Does this imply that dual range is required for CO & O2? 28A. Two points indicate a standard daily calibration check, with zero as point one and span as point two. 29.Section 2.1.4: This section states that the Contractor shall disconnect the existing opacity monitors from existing transmitters and remove the transmitters from the current cabinet. Does this imply: a. That the entire opacity monitor system is to be removed and never used for the new CEMS systems on unit #5 #6 (i.e. transmissometers and reflectors on the stack AND the rack-mounted opacity controller within the existing CEMs cabinet at grade level) b. Just the rack-mounted opacity controller within the existing CEMs cabinet at grade level and never used for the new CEMS systems on unit #5 #6? c. Removing just the existing rack-mounted opacity controller from the old CEMS cabinet at grade level and reinstalling in the new CEMS? 29A. The correct answer is a. That the entire opacity monitor system is to be removed and never used for the new CEMS systems on unit #5 #6 (i.e. transmissometers and reflectors on the stack AND the rack-mounted opacity controller within the existing CEMs cabinet at grade level) MAJ Carl J. Gorkos II / carl.gorkos@amedd.army.mil Comm: (301) 619-2110 /Mobile: (301) 978-1201 /Fax (301) 619-2680 SUBMITTAL INSTRUCTIONS 1)Proposal may be submitted electronically or by hard copy via the following procedures: a)Electronic Submission. Submit electronic proposal via e-mail to MAJ Carl Gorkos at carl.gorkos@amedd.army.mil b)The Government will not be responsible if your entire proposal package does not transmit electronically and is not received. Contractors should send a separate follow-up message to confirm receipt. c)Hard Copy Submission. Hard copy submission should be mailed or hand carried to: U.S. Army Medical Research Acquisition Activity ATTN: MAJ Carl Gorkos Solicitation No: W81XWH-12-R-0065 Bldg. 820 820 Chandler Street Fort Detrick, MD 21702-5014 2)Proposals will be submitted in the following format. a)Technical Proposal: i)Offeror shall submit one electronic file or hard copies (one marked "Original", and three copies), with the following characteristics: (1)8 " x 11" format (2)12 point font (3)Limited to 30 pages ( page count excludes schedule, cover page, and tabs). Pages that EXCEED the page limitation SHALL NOT be evaluated. (4)Include a cover page with Solicitation Number, Solicitation Title, Prime Contractor Name, Address, Phone Number, Fax Number, DUNS, Cage Code, Point of Contact and their phone and email address. b)Price Proposal: i)Offeror shall submit one electronic file or hard copies (one marked "Original", and three copies). View Solicitation Amendment 0001 for responses to questions and Title V Permit requirements. Site Visit Questions from CEMS Ft Detrick, MD / Sol: W81XWH12R0065 Please respond with your questions by 10:00 am, 07 September, 2012. I will have the Technical Representative answer the questions and I will compile and post them for all. After discussing the solicitation close date with the Contracting Officer, The solicitation close date is now Thursday, 20 September, 2012. Proposals will be due by 2:00 pm that day. This is a combined synopsis/solicitation for commercial items prepared in accordance with the format in Subpart 12.6, as supplemented with additional information included in this notice. This announcement constitutes the only solicitation; proposals are being requested and a written solicitation will not be issued. SCHEDULE CLIN ITEM NO: 0001 SUPPLIES/SERVICES; Continuous Emissions Monitoring Systems Contractor shall provide all equipment, material, services, and labor to furnish and install a new Continuous Emissions Monitoring Systems for two (2) Medical / Infectious Waste Incinerators located in the Departmentof Public Works, 393 Beasley Drive, Fort Detrick MD 21702. QUANTITY: 1 Each (Consists of 2 CEMs Monitors) CONTRACT TYPE: FFP FOB: Destination CLIN ITEM: 0002 SUPPLY/SERVICES: Contractor Manpower Reporting QUANTITY: 1 Each CONTRACT TYPE: FFP FOB: Destination MINIMUM ESSENTIAL CHARACTER, STATEMENT OF WORK/ MINIMUM ESSENTIAL CHARACTERISITICS, HMIWI CEMS REPLACEMENT Part 1 - General Information 1. General: This requirement calls for the contractor to furnish and install equipment to replace the current HMIWI CEMS. 1.1 Description of Requirement: The contractor shall provide all personnel, equipment, supplies, facilities, transportation, tools, materials, supervision, and other items and non-personal services necessary to provide HMIWI continuous emissions monitoring systems replacement as defined in this Statement of Work except for those items specified as government furnished property and services. The contractor shall perform to the established commercial industrial standards and any specific requirments in this contract. 1.2 Background: The U.S. Army Garrison (USAG) Fort Detrick is located in Frederick, Maryland. Air emissions are governed by the U.S. Environmental Protection Agency (USEPA) and Maryland Department of the Environment (MDE). Fort Detrick is located in an ozone non-attainment area, in terms of air quality, and must meet many varied emissions monitoring and reporting requirements imposed by the EPA and MDE. Fort Detrick's Clean Air Act Title V Part 70 Operating Permit, which was issued on November 1, 2009, requires continuous operation of EPA-certified continuous emissions monitoring systems on the two HMIWIs. 1.3 Objectives: The objective of this contract is to replace the current (older) CEMS equipment with new CEMS equipment to meet the requirements of 40 CFR 60 for the two CEMS units andprovide EPA-required startup calibration and certification, training and disconnection of existing opacity monitors. 1.4 Scope: The contractor, as an independent contractor and not as an agent of the Government, shall use its technical expertise in the subject areas to provide equipment, installation, EPA-approved calibration and certification, and training to meet the requirements of 40 CFR 60; and to disconnect existing opacity monitors from transmitters and remove transmitters. 1.5 Period of Performance: The contractor shall have 180 days from the date of award to furnish and install the equipment. 1.6 General Information 1.6.1 Quality Assurance: The contractor is expected to conducts its own inspection of the work as the equiopment is being installed following its own standard commercial practices to ensure a quality installation and that the equipment performs per the manufacturers specifications. The contractor shall provide a quality assurance report twice during performance. The first after installation is completed and the second after the equipement has successfully pasted the testing and inspection and is performing as intended IAW manufacturers specifications. 1.6.2 Recognized Holidays: The contractor is not required to perform work on the following Federal Holidays: New Year's Day, Labor Day, Martin Luther King Jr.'s Birthday, Columbus Day, President's Day, Veteran's Day, Independence Day, Memorial Day, Thanksgiving Day, Christmas Day 1.6.3 Hours of Operation: HMIWI units must be able to run 5 days a week (Monday thru Friday), 20 hours per day (0600 - 0200). The Government/ US Army Fort Detrick Garrison Director of Public Works plans to allow for the shutdown of one of the two incinerators and CEMS to allow for the installation of one new system. After that new system Fabrication and installation work may not interfere with this schedule, and shutdowns must be coordinated in advance with the plant supervisor. Existing continuous emissions monitoring system or incinerator/scrubber may be shutdown as needed after approval by the supervisor. The plant is open and accessible from 0600 - 2200 Monday through Friday, and can be opened at other times as requested. Facilities such as locker room, break room, and bath room are for the use of plant employees. Contractors shall supply amenities to meet the needs of site workers as needed. Parking is limited and cannot impede the day-to-day operations. All parking, except loading and unloading should be done in a designated parking space. Storage space for tools and parts is limited and should be coordinated with the supervisor. All materials demolished and removed from the site are the property of Fort Detrick and shall be returned to the supervisor. 1.6.4 Place of Performance: The work to be performed under this contract will be performed at Bldg. Bldg. 393 Beasley Drive, Directorate of Public Works, Fort Detrick, MD 21702. 1.6.5 Type of Contract: The government will award a firm fixed price contract. 1.6.6 Security Requirements: The Contractor shall ensure all personnel performing under this contract have a favorable National Agency Check with Written Inquires (NACI), which must be coordinated with the USAG Security Office for submission within three business days prior to performance start date. The security requirements must be maintained for the life of the contract, and citizenship will be verified by the Security Office on all contract personnel. 1.6.6.1 Physical Security: The contractor shall be responsible for safeguarding all government equipment, information and property provided for contractor use. 1.6.7 Special Qualifications: All original materials, visual aids, software and text developed in performance of the Specifications listed herein will be the property of the Government. The contractor or persons employed by or in any way responsible to the contract in respect to accomplishment of this Statement of Work shall make themselves available to respond to technical issues. Technical issues are perceived to be any operational or structural difficulty encountered in explaining results and methodology. The contractor shall, without additional expense to the Government, be responsible for obtaining any necessary licenses and permits and for complying with any Federal, State and local laws, codes and regulations applicable to the performance of this work. 1.6.8 Post Award Conference/Periodic Progress Meetings: The Contractor agrees to attend any post award conference convened by the contracting activity or contract administration office in accordance with Federal Acquisition Regulation Subpart 42.5. The contracting officer, Contracting Officers Representative (COR), and other Government personnel, as appropriate, may meet periodically with the contractor to review the contractor's performance. At these meetings the contracting officer will apprise the contractor of how the government views the contractor's performance and the contractor will apprise the Government of problems, if any, being experienced. Appropriate action shall be taken to resolve outstanding issues. These meetings shall be at no additional cost to the government. 1.6.9 Contracting Officer Representative (COR): The (COR) will be identified by separate letter. The COR monitors all technical aspects of the contract and assists in contract administration The COR is authorized to perform the following functions: assure that the Contractor performs the technical requirements of the contract; perform inspections necessary in connection with contract performance; maintain written and oral communications with the Contractor concerning technical aspects of the contract: issue written interpretations of technical requirements, including Government drawings, designs, specifications: monitor Contractor's performance and notifies both the Contracting Officer and Contractor of any deficiencies; coordinate availability of government furnished property, and provide site entry of Contractor personnel. A letter of designation issued to the COR, a copy of which is sent to the Contractor, states the responsibilities and limitations of the COR, especially with regard to changes in cost or price, estimates or changes in delivery dates. The COR is not authorized to change any of the terms and conditions of the resulting order. 1.6.10 Key Personnel: The contractor shall provide the name of a project manager who shall be responsible for and oversee the performance of the work. The name of this person and an alternate who shall act for the contractor when the project manager is absent shall be designated in writing to the contracting officer. The project manager and alternate shall have full authority to act for the contractor on all contract matters relating to daily performance of this contract. The project manager or alternate shall be available as in section 1.6.3 above. 1.6.11 Identification of Contractor Employees: All contract personnel shall wear identification badges that clearly show they are not Government employees. Government employees working on-site, attending meetings,, and working in other situations where their contractor status is not obvious to third parties are required to identify themselves as such to avoid creating an impression in the minds of members of the public that they are Government officials. They must also ensure that all documents or reports produced by contractors are suitably marked as contractor products or that contractor participation is appropriately disclosed. 1.6.12 Site Visit: A site visit for this requirment will be conduced on 5 September 2012 at 10:00am at Bldg. 393 Beasley Drive, Fort Detrick, MD 21702. Intersted contractors should call the Contracting Officer at 301 619 2110 to be scheduled for the visit. 1.6.13 Anti-Terrorism Level One Training: All contractor employees, including subcontractor employees, requiring access to Army installations, facilities, or controlled access areas shall complete AT Level I awareness training within 15 calendar days after contract start date or effective date of incorporation of this requirement into the contract, whichever applies. The contractor shall submit certificates of completion for each affected contractor employee and subcontractor employee to the COR (or to the contracting officer, if a COR is not assigned) within 15 calendar days after completion of training by all employees and subcontractor personnel. AT Level I awareness training is available at http://www.detrick.army.mil/ready/iwatch.cfm. If training is required in a non-English language, please contact Fort Detrick ATO at usagantiterrorism@amedd.army.mil. All contractor employees must complete annual AT Level I awareness training 1.6.14 iWATCH Awareness: The contractor and all associated subcontractors shall brief all employees on the local iWATCH program (training standards provided in this PWS by the Fort Detrick ATO). This locally developed training will be used to inform employees of the types of behavior to watch for and instruct employees to report on suspicious activity to the COR. This training shall be completed within 30 calendar days of contract award and within 30 calendar days of new employees' commencing performance, with the results reported to the COR no later than 5 calendar days after completion. All training materials can be found at http://www.detrick.army.mil/ready/iwatch.cfm. Part 2 FUNCTIONAL SPECIFICATIONS AND MINIMUM ESSENTIAL CHARACTERISTICS 2. Recommended Functional Specifications: 2.1 General: The contractor shall provide all labor, materials, equipment, tools and management services necessary for proper and complete replacement of two continuous emissions monitoring system. All equipment shall be submitted and approved before purchase. If equipment is purchased before it is approved, it can be returned to the contractor at no cost or obligation to the government. Without restricting the generality of the foregoing, the following items of work are included: Gas extractive probe, tubing and conditioning equipment, analysis enclosure assembly, oxygen and carbon monoxide analyzers and recorder, calibration gas cylinders and rack, data acquisition, alarm, and signal processing, automatic calibration and certification, installation supervision, start-up, and certification. The CEMS monitors and records flue gas oxygen, carbon monoxide, and other flue gas parameters as required for this project and for compliance with MDE and other pertinent regulations. Output signals from the CEMS will be used to: 1) drive interlocks to prevent charging during upset conditions; 2) provide warnings and alarms to operating personnel, enabling them to make timely manual adjustments; and 3) provide continuous record of flue gas properties as required for regulatory compliance. The CEMS will measure carbon monoxide and oxygen. Contractor shall also disconnect existing opacity monitors from existing transmitters and remove the transmitters from the current cabinet. The following products (or the acceptable equivalent) shall be used: ThermoFisher 43i CO and Servomex 1440D O2 Analyzers, GE QuickPanel Jr Display, M&C Sample Conditioner. Equipment - equipment proposed prior to award is what the Government expects to be furnished and installed. Contractor shall provide specification submittals for this equipment after award but prior to actual istallation. Any chnges to the equipment originally proposed must be submitted and approved by the COR and Contracting Officer. 2.1.1 Design Requirements: Each instrument shall include a readout on the analysis enclosure. All readouts shall be digital and of consistent appearance. Each will plainly identify the parameter it measures and the numerical value of the parameter, without scale factors. If a dual-range instrument is provided, readout shall show only the numbers for the range currently in use. Each instrument shall provide at least one 4-20 mA output and have provision for instantaneous or time-averaged output with selectable and labeled periods of averaging. The 4-20 mA outputs shall have ungrounded negatives and be suitable for an impedance of up to 500 Ohms. Each instrument shall be equipped for automatic self-calibration, selectable for manual or periodic automatic initiation. During calibration, a panel lamp shall light and the last parameter value prior to calibration shall be held and conveyed to output. Panel readout shall preferably display, by switch selection, either the held value or the calibration output. Automatic, self-calibration may be accepted if triggered as a group from the Data Acquisition System, in lieu of each individual part. 2.1.2 Gas Extraction & Conditioning Equipment: The gas extraction and conditioning equipment shall deliver a continuous sample of gas to the analysis enclosure in a way that allows the instruments therein to measure their respective constituent gases with consistent high accuracy and freedom from instrument damage and deterioration. It shall accomplish the following: 2.1.2.a. Withdraw the sample through a probe of materials suitable for long-term exposure to the waste stream without degradation. A non-dilution extractive, probe is preferred. A dilution type probe will be considered if it meets all regulatory requirements and entails no extra operating cost for more frequent calibration. 2.1.2.b. Provide at least two stages of filtration with media resistant to blinding under the proposed conditions. 2.1.2.c. Provide a means for detection of increased differential pressure in the probe and filters. 2.1.2.d. Provide a means for automatic periodic backflushing of the gas path, including probe and filters, with clean air. 2.1.2.e. Remove moisture from the sample stream down to a water vapor or acid dew point of not more than 115 F and not less than 30 F below the lowest steady or transient system or instruments. Method of moisture removal must not change the concentrations of gases to be monitored. 2.1.2.f. Conduct the sample to the analysis enclosure in tubing with teflon or stainless steel liner, insulated and heat traced using thermostatic self-limiting tracing elements in such a manner as to assure that the sample stream will stay at least 30 F above the dew point of any condensible component of the stream. 2.1.2.g. Provide a means for remote-actuated injection of calibration gases to the sample line at a point as close as practical to the probe inlet. 2.1.2..h. Provide the means to pump the sample stream from the source through the instruments. 2.1.3 Analysis Enclosure Assembly: The analysis enclosure will house and protect the analysis instruments, sample and calibration gas manifolds, flow meters, means for controlling automatic calibration cycles, and necessary electrical interconnections. 2.1.3.a. Analytical Instruments: Each analyzer shall be shop and field tested in accordance with the performance requirements of EPA procedures and specifications in 40 CFR 60 Appendix B and as subsequently amended relative to accuracy testing. Each instrument shall meet or exceed the following requirements: Repeatability - 0.5% full scale; noise - < 0.5% full scale; span drift - < 1% full scale per week; zero drift - < 1% full scale per week; response time to 80% of step - < 3 seconds @ 1 liter/minute; response time to 95% of step- < 6 seconds @ 1 liter/minute; linearity - 1% of full scale, entire range; operating temp - 0 to 120 F; operating relative humidity - 0 to 95% RH; sample flow rates - 0.5 to 1.5 liter/minute; power input - 115 VAC 10%, 60 Hz, 1 Phase; output - isolated 4-20 mA linear with measured variable, suitable for a load of up to 500 Ohms. Each instrument shall have a built-in diagnostic system and alarm to signal a malfunction in any of its parts, and will, to the extent practical, indicate the location of the malfunction or annunciate the part that has failed. Response of any instrument to interfering gases shall not be more than 0.01% of its response to the gas it is intended to measure. Each instrument shall have an LED display with automatic floating decimal point. 2.1.3.b. Oxygen Analyzer: The oxygen analyzer shall meet all general requirements above, and the following: minimum range - 0.1 to 20.9% 02; resolution - 0.1% or better; calibration error - < 5% of reading; minimum detectable limit - < 0.2% full scale. The two point daily calibration shall utilize the same span gas requirements as other equipment in the plant. The specifications for the span gas are 22.5% O2, the balance will be nitrogen for use in the CO zero. 2.1.3.c. Carbon Monoxide Analyzer: The carbon monoxide analyzer shall meet all general requirements above, and the following: minimum range - 0 to 500 ppm; resolution - < 1% of full scale; accuracy - < 2% of full scale; minimum detectable limit - < 0.2% full scale. The two point daily calibration shall provide for the zero O2 and the CO span to mixed in the same bottle 2.1.4 Calibration Gas Cylinders: Vendor shall supply calibration gases sufficient to calibrate at least two (2) points in the range of each analytical instrument. Gases shall be traceable to NIST standards. A regulator and two (2) pressure gauges shall be supplied for each cylinder. Regulators and gauges shall be of corrosion-resistant materials, not affected by any of the calibration gases being regulated. A sufficient quantity of gases shall be supplied for a typical course of startup testing plus six (6) months normal operation. Automatic calibration is required for all instruments in accordance with Title 40 of CFR, except as noted. 2.1.5 Data Acquisition, Alarms and Signal Processing: A complete data acquisition system shall be supplied to collect and process analyzer outputs from the analytical systems. This system will integrate each analyzer, provide for automatic zero and span calibration, display system status, and alarm functions on an annunciator panel, and produce reports concurrent with regulatory requirements. The data acquisition system shall be an integral part of the analyzer system, and shall be enclosed in a case suitable for standard 19 inch rack mounting, either in conjunction with the analyzer/sample conditioning cabinet, or in a separate cabinet, as space dictates. The system shall consist of an IBM or compatible (MS DOS) computer with monitor and printer, annunciator display, all necessary software, hardware, and interfaces. Operating systems other than that described herein will be considered provided the functional and reporting requirements are not compromised. It is a requirement that the Data Acquisition System shall be provided by the vendor providing the CEM analyzer equipment to ensure single vendor responsibility for the entire CEM system. The data logging and acquisition system shall meet all relevant EPA and MDE requirements. 2.1.5.a. Hardware and Operating System Requirements: All computer cabling for connection between CEM analyzer cabinet and the CEM data acquisition system shall be provided under this section. The computer system shall be mounted in a free standing NEMA 12 enclosure with the following features: fold down shelf for keyboard with keylocks; printer carriage; monitor screen.section with safety glass and hinged door and keylock; removable sidewalls and rear door to provide access from all 4 sides; rack mounting system (with ventilated system)for computer and uninterruptible power supply; power receptacle for components; 14-gage rear door construction with 16 gauge sidewalls; central locking system. To meet the need for continuous compliance monitoring, the system shall be capable of operating 24 hours per day and 7 days per week. Consequently, all hardware components shall be of industrial design and packaged for sustained operation. Provide as a minimum, the following hardware elements for mounting in the computer enclosure described above: 1 TB hard drive; 8 GB random access memory; writable DVD drive; industrial rack mount computer; "qwerty" keyboard and mouse must be accessible in the enclosure; minimum 19 inch LED color monitor; laser jet printer; internal or external fax/modem or network connection (system can apply for connection to the Ft Detrick LAN if it has a "certificate of net worthiness" acceptable to the NEC Office); rack mountable uninterruptible power supply (that can sustain the system for a minimum of 1 hr during loss of power). The data shall be displayed as real-time gauges and trending graphs. Two monitor/keyboard terminals and drives shall be provided. Accessing the computer system from remote terminals as well as from the main terminal or the internal modem/network shall be an integral part of design. The dual external hard drive, minimum size 1 TB, shall provide for daily automatic backup of compliance data. As a minimum, the following software elements shall be provided: For real-time, alarm management and on-line analysis, the operating system shall contain multi-Specificationing features and operate in a real-time environment. The operating system shall allow. multi-user capabilities and the ability to add multiple terminals without changes in the source code. The multi-Specificationing, multi-user operating system shall allow access to current or past data at the same time the system is continuously collecting and storing data from on-line compliance monitoring instruments. Configuration files in the Data Acquisition Systems shall allow access to customize and generate reports that meet EPA, state and local monitoring requirements without changes in the source code. The capability to change, modify or add reports while the computer system is acquiring data shall be provided. 2.1.5.b. Minimum System Requirements: The computer system shall be menu driven to allow ease of access to real-time and archived data, generation of reports, and editing of archived data. The following shall be offered: (1)The ability to view real-time tables of incoming data and view real-time color gauges; (2)The ability to view X-Y plots of data collected in the past hour or day over a specified day, week, month or quarter shallbe provided; (3) The ability to calculate averages of incoming data over a specified time period for EPA certification; (4) The system shall log disruptive incidents (units down, instruments out of service, measurement parameters-out of control) as they occur; (5) The ability to edit the constants used in data reduction and report generation; (6) The ability to edit the historical data, incident reason codes, and incident comment codes; (7) The ability to generate a variety of application specific reports without changing the source code; (8) The ability to set up automatic archiving to dual external hard drives containing duplicate date or mainframe computer; (9) The ability to identify and display the ten highest or lowest recorded parameters for each dataset with date, time and parameter displayed for the time period selected. The Data Acquisition System shall be able to compile data from any Continuous Emissions Monitoring System (CEM), other individual monitoring instruments such as gas flow monitors, and many additional sources, including the controllers for data read from extractive (pump-driven sampling) and dilution extractive instruments. The datasets shall be as listed: Boiler temperature, Cabinet Temperature, CEMs OK, CO, CO 12 Hr, CO Corrected, CO Hr, CO Min, CO Raw, Instantaneous Weight, Last Weight, Total Weight (current hour), Total Weight (last hour), 02, Primary Temperature, Sample Temperature, Scrubber Fan Temperature, Scrubber Amps, Scrubber Flow, Scrubber pH, Secondary Temperature, Secondary Temperature Limit, Unit On/Off, Charge Weight. This list may not be all inclusive, but will be a minimum set of data recorded for each of the two HMIWIs. 2.2 Instrumentation: The contractor shall provide all labor, materials, equipment, tools and management services necessary for proper and complete fabrication and shipping of instrumentation. Without restricting the generality of the foregoing, the following items of work are included: panel mounted instruments, scrubber and incinerator control panel, annunciator. All equipment shall be of the best quality and workmanship and shall be as manufactured by companies indicated in this specification. The electrical power available is 480 volt 60 Hertz 3 phase with a normal variation of plus and minus 10 percent. All devices shall operate continuously and accurately under the above conditions. At times spikes, surges, ripples and dips will be experienced which exceed the above limitations. All devices shall be furnished with suitable protection from damage when these excursions occur either by internal circuitry or external protection. Operation is not required when these excursions occur. In the event of a power outage, spike, surge, ripple, or dip, all devices shall return to accurate operation automatically within 15 seconds. Available placement for instrumentation is in a location with possible extreme temperatures and dust; enclosures should protect and condition the contents to prevent damage to the 2.2.1 Panel Contents: So as to provide a uniform and pleasing appear ance, all front of panel devices shall be of the same manufacturer and model line wherever possible. All rear of panel devices shall be of the same manufacturer and model line wherever possible so as to minimize spare parts stocking. 2.2.1.a. Indicator/Recorder will include: Scrubber pressure drop, secondary chamber temperature, primary chamber temperature, carbon monoxide and oxygen. 2.2.1.b. H-0-A selector switches, system/power on-off switches, status lights and other devices as required for a safe and integrated panel with the incinerator control panel. 2.2.1.c. Summary of System Interlocks (all safety interlocks shall be user programmable with adjustable setpoint to meet changing conditions) ParameterWaste Loader Secondary Temperature Below 1700 F at startupOFF Below 1700 F during operationON Below 1700 F during operation for 15 minutesOFF Above 2000 FOFF Primary Temperature Draft 0.02 inches (after 5 seconds)OFF Carbon Monoxide (CEMS) Above 100 ppmv after 15 minutesOFF Scrubber Low recirculating waterOFF pH out of rangeOFF High inlet temperatureOFF AP across scrubber out of rangeOFF Note: Provide other operational/safety interlocks as required. 2.2.1.d. Summary of Emergency Interlocks:The following emergency conditions shall cause the by-pass damper to open and shut-down the entire system: power failure, scrubber failure, system failure. Boiler Failure shall cause the by-pass damper to open and the burners to turn off. By-pass damper proof of closure switch failure shall cause the burners to turn off and the waste loader to be locked. Some of these processes are controlled through either the incinerator or scrubber controls. 2.2.1.e. Annunciators: An operator interface panel with monitor and alarm screen shall be supplied in conjunction with PLC. At minimum, the following alarms shall be displayed: high secondary combustion chamber temperature, primary burner failure, secondary burner failure, scrubber high temperature, scrubber high differential pressure, low boiler water, high boiler water, high steam pressure, high carbon monoxide, low oxygen, low water flow to scrubber, CEMS failure. Provide an auxiliary relay for remote alarm station. Relay shall have normally open contacts. Provide 3 No. 14 AWG wires from relay to junction box mounted on the outside of the incinerator building south wall. Relay shall provide 48 VDC signal under normal conditions. Any alarm condition shall deenergize relay and interrupt 48 volt signal. Annunciator can be incorporated into programmable logic controllers operator interface as described in 2.2.2.c., but must meet all the above conditions. 2.2.2. Products: 2.2.2.a. A continuous trending graph "page" accessible on the main monitor of the DAHS, that is capable of displaying user selectable, multiple trends able to display history to any recorded date and time. 2.2.2.b. 24-VDC Power Supply System: Power supplies for converting 120 volt AC source to 24 volt AC and DC shall include the following: Integral circuit breakers for 120 volt AC and 24 volt AC; power supply operating light; integral voltage and current meters; integral voltage and current limiting for 24 volt DC output; integral low voltage alarm contacts. Power supplies shall be designed for standard 19-inch rack mounting. All wiring shall be accessible from the front. Forced cooling shall not be required for proper power supply operation. Power supplies shall be designed for parallel operation and automatic load sharing such that if one supply fails, the entire system will remain operable. 24 VDC battery operated back-up supplies shall be furnished which will operate the analog system for a minimum of 1 hour after loss of main power. The battery supplies shall have low voltage cutoff and ready indicating light. Batteries shall be sealed type (non- venting). Supply shall include an integral charger and regulator circuit operated from a 120 volt AC source. Battery supply shall automatically reset upon return of main 24 VDC. 24 volt AC, 24 volt DC main and 24 volt DC auxiliary power to instruments and accessory equipment shall be via individual circuit breaker modules. Circuit breaker modules shall be consolidated in one location. Main and auxiliary 24 volt DC power shall be connected to each individual system component. Power supplies shall be operable over the temperature range of 32 to 120 F. 2.2.2.c. Programmable Logic Controllers: Construction shall be modular printed circuit boards with motherboard mainframe. Type shall be electronic components with software reprogramming capabilities. Memory shall be retentive on normal power supply failure. Memory reprogramming loader shall be provided. Language format shall bed ladder type diagrams. Programming panel display shall be Eaton PANELMATE EPRO PS, with 8" TFT Display, equivalent or better (Operator Interface Terminal). Digital inputs shall be as required plus 20 percent spare. Digital outputs shall be as required plus 20 percent spare. Internal functions shall be relays, timers, counters, latches, as required, and as described herein plus 50 percent spare memory. Operating temperature shall be 20 F to 140 F. Storage temperature shall be minus 40 F to 140 F. Environmental rating shall be NEMA 4. Power supply shall be 120 VAC 10 percent with fuse or circuit breaker protection. Battery type shall be nickel-cadmium for 1 year back-up. Key interlock security shall be provided to prevent operator tampering of logic sequences on lines. Contractor shall supply wiring diagrams; cross references and detailed mnemonic titles shall be included. 2.2.2.d. Control Panel: Panel shall be NEMA 12 construction. Contractor shall provide subpanels for terminal strips and internally mounted devices. Contractor shall design and size all panels to provide ample room for locating components, wiring and piping so that connections can be easily made and there is ample room for servicing each item. Panel shall support and restrain all internally mounted components and flush mounted deep case or shelf mounted instruments to prevent any undue movement. Contractor shall provide all instruments, wiring, piping and any other components necessary to make each panel a complete workable tested unit. Contractor shall be responsible for the detailed arrangement and construction of the panel. Cutouts are to be based on instrument vendor's requirements. All internal wiring shall be in covered plastic raceways. All materials shall be new and shall conform to the requirements of this Specification. Materials shall be of high grade, free from defects and imperfections and of recent manufacture. Access doors shall be pan type, not to exceed 24 inches wide. Contractor shall provide full length concealed piano hinge for each door, except when otherwise specified and handle operated, key-lockable 3-point latching mechanism. Contractor shall provide continuous oil resistant gasket around each door and 5/8-inch anchor bolt holes in the bottom of enclosure. All steel subpanels, brackets, supports, etc. shall be painted with 2 coats of semi-gloss white lacquer after proper preparation and priming. Panels shall have rear doors where permitted by panel locations. Where rear doors are not possible, side and/or front doors shall be used. No devices other than lights, switches, or pushbuttons shall be located on doors. Indicators and controllers shall be located between 3 feet and 6 feet above the floor. Lights, switches and pushbuttons can be located as low as 30 inches above the floor. Annunciators can be as high as 7 feet above the floor. All openings for conduits or piping shall be sealed watertight. The conduits shall also be sealed watertight. The panels are to be constructed of twelve gauge (minimum) steel panels on 10 gauge welded steel frame adequately braced and stiffened to maintain a flatness of 1/16 inch over any two foot span. The front shall be 7 gauge (minimum) sheet steel. Contractor shall continuously weld all seams and provide 5/16 inch diameter copper ground studs, making a clean metal contact with the frame structure, which will be the ground connection points for all the panel equipment. A clean, 1 inch diameter area, void of any paint, shall be provided around each stud. After fabrication, the enclosure shall be cleaned, surface prepared and painted in accordance with the following procedure: 1) All areas requiring surface preparation shall be washed with either naphtha, mineral spirits or lacquer thinner in order to remove all oil, grease and dirt. The Contractor shall ensure that all hydrocarbon cleaning solvents are properly disposed. 2) Exterior surfaces shall be surface ground to completely remove all corrosion and mill scale. The interior shall be wire brushed to remove all welding scale and corrosion. 3) Fillers shall be used to cover pits and blemishes and ground smooth to remove high spots and excess filler when dry. All external welds and seams shall also be ground smooth. 4) All interior, and exterior surfaces shall be zinc-phosphatized prior to primer application. 5) One coat of primer shall be applied to all interior and exterior surfaces immediately. Exterior surfaces shall then be given sufficient coats of primer surfacer, applied with sanding and cleaning between coats, until a Grade 1 finish (super smooth; completely free of imperfections) can be produced on the finish coat. 6) All interior surfaces shall be painted with 2 coats of semigloss white enamel. 7) All exterior surfaces shall be painted with a minimum of three (3) finish coats of polyurethane to ultimately produce a Grade 1 finish. Color to be selected by Owner from color charts furnished by the Contractor. Provide one extra quart of touch-up paint for each exterior finish color after field touch-up has been completed. 8) Primer and finish paint shall be compatible. All panels shall have Volatile Corrosion Inhibitor (VCI) blocks. Sufficient VCI for two years shall be furnished. The panels shall be equipped with fans or solid state heat exchangers to prevent any panel items from exceeding their temperature ratings. All openings for fans shall have adequate filters. Filter replacement shall not require the removal or disassembly of any panel components. 2.2.2.e.(1) Identification: Contractor shall provide nameplate with 11 inch letters to identify a given panel, provide nameplate with 3/16 inch letters for each panel mounted device, and nameplates shall be constructed as follows: 1) 3/32 inch thick laminated phenolic for engraving composed of core, laminated on both sides with a matte (non-glare) finish cover sheet. 2) Core to be black; cover sheet to be white. Front face beveled edges to be 1/32 inch by 45. 3) Mounting holes to be centered on width and inch from each end. Contractor shall provide two stainless steel self-taping screws per nameplate. All rear of panel devices shall be provided with engraved phenolic nameplates as specified above, secured as specified above. 2.2.2.e.(2) Electrical Systems: When DC power and/or low voltage AC power is required, contractor shall provide and install the necessary power supplies and transformers in the panel. Provide air circuit breakers to protect each circuit of no more than six instruments; supply minimum two spare breakers. Provide a 40-watt fluorescent service light within the enclosure and an easily accessible switch near access door. Provide a 120 VAC duplex convenience outlet within the enclosure located so that it is accessible from access door. The service light with switch and duplex outlet shall have its own separate breaker and shall be wired to terminals at one end of the control terminal blocks for connection to an external 115 volt, 60 Hz power source. Provide complete wiring diagram showing "as built" circuitry in point to point format. Diagram shall be enclosed in transparent plastic and placed in easily accessible pocket built into panel door. Panels having voltages of 208 AC and above shall be provided with a door label reading "WARNING - HIGH. VOLTAGE." Applicable Standards: All cable, conduits, stands, supports and appurtenances shall be in accordance with instrument manufacturer's recommendations, this section, and relevant API, ISA, SAMA, and NEC specifications. Wiring: Internal wiring shall be Type THHN color coded stranded copper wire. For DC signal wiring, use No. 18 minimum AWG shielded. For AC power wiring, use No. 14 minimum AWG. For wiring carrying more than 15 amps, use sizes required by NEC and JIC standards. Install wiring runs in wire troughs along horizontal or vertical routes to present a neat appearance. Angled runs are not acceptable. Group or bundle parallel runs of wire using covered plastic troughs. Maximum bundle size to be 1 inch. Troughs shall have 40 percent spare capacity. Separate and shield DC signal wiring from power and control wiring by a minimum of 6 inches. Adequately support and restrain all wiring runs to prevent sagging or other movement. Lacing with twine is not acceptable. Use insulated crimped fork or ring lugs at termination. All wiring shall be installed such that if wires are removed from any one device, power will not be disrupted to any other device. Each wire shall be marked at each end via a permanent marker on the wire corresponding to the wiring diagram. Use barrier type terminal strips with screwed connections, 600 V rating, and numeric identifiers beside each connection. Terminals for AC power shall be rated 30 amps. Soldered type connections are not acceptable. Provide spare terminals equal in number to 20 percent of the terminals used for each type of wiring (DC signal and AC power). All ground terminals of receptacles shall be wired to the frame of the control panel. The enclosures of all equipment receiving a power supply shall be solidly grounded. One ground terminal shall be installed in, each panel, for connection to plant (electric systems) ground. A separate, isolated ground pad shall be established for the electronic (signal) ground, and for the connection to all terminal blocks for instrument wire shield and/or drain wire. This pad shall be grounded to a separate ground or to the plant ground as per recommendations by the Instrument Manufacturer. Each ground pad shall accommodate #6 AWG wires, the isolated pad shall include space for two (2) extra #6 lugs. All ground wires shall be green with yellow tracer, or tape. Where wires pass through panel walls, provide suitable bushings to prevent cutting or abrading of wire insulation. Relays shall be of the long life, heavy duty plug-in type with transparent dust covers, front connected terminal lugs on base and a locking device. Contacts shall be rated 10 amps at 115 V. Contacts for instrument signals shall be noble metal 2 amps at 115 V. Relays for more than 10 amps shall be heavy duty machine tool type. Panel Devices: Rotary type pilot switches, minimum number of poles as required, contacts rated 10 amps, 115 V. Switches for instrument signals shall have noble metal double throw contacts rated at 2 amps, 115 V for panel mounting. Heavy duty, industrial oiltight indicating lights and pushbuttons, operating on 115 volt, 60 Hz, shall be a minimum 1 7/16 inch square for a unit of two indicating lights or operators. Indicating lights shall be for operation on 24 volt or below, with long life bulbs. Buttons or lenses shall have legends and perform functions according to drawings. All units shall be insulated for 600 volt. 2.2.2.f. All enclosures shall be climate controlled to reduce humidity and keep cabinet temperatures at 80 degrees Fahrenheit or below. Climate control systems shall be installed in such a way as to prevent equipment from impeding airflow throughout the entire cabinet so that heat generated by the equipment can circulate freely and be exchanged. HVAC systems should have adjustable thermostats and condenser inlet air filters that can be cleaned or replaced. 2.2.2.g. Field Tests and Inspections: Upon completion of installation of each piece of equipment, the Vendor shall field inspect and mechanically and electrically test equipment for proper function. Each instrument shall be calibrated at 0, 25, 50 and 90 percent. The loop diagrams shall be complete at this time. 2.3 Field Service. Contractor shall provide 6 days of on-site installation, startup and commissioning. Contractor shall prove conformance to contract documents by demonstrating the following: Operating sequences and shut-down sequence, safety interlocks for entire system according to Instrumentation section, alarm conditions and fail-safe shut-downs, and setpoints during normal operation. 2.4 Warranty. The Manufacturer shall guarantee new equipment and work specified herein against any defects in workmanship, material and performance for 2 years after commercial operation date or 30 months after delivery. If, during the period of one year from final written acceptance, any defects in workmanship, material or performance should appear, the Manufacturer shall remedy them without cost to the Owner. 2.5 As-built drawings. Upon completion of the project three complete sets of as-built drawings, to include accurate equipment layouts, flow diagrams, electrical schematics, equipment cut sheets, and ladder logic diagrams shall be provided. In addition, back-up copies of all unique software, and three copies of a quality assurance/quality control plan detailing proper operation and maintenance of the completed system shall be provided. Part 3 Applicable Publications 3. Applicable Publications (Current Editions) : 3.1. All Electronic and Information Technology (EIT) procured through this Specification must meet the applicable accessibility standards at 36 CFR 1194. If the applicable accessibility standards have not been identified prior to award, they may be incorporated after award. Such action after award may be a basis for the contractor requesting an equitable adjustment. 36 CFR 1194 implements Section 508 of the Rehabilitation Act of 1973, as amended, and is viewable at http://www.access-board.gov/sec508/508standards.htm - Part 1194. Part 4 Attachment/Technical Exhibit Listing 4.Attachment/Technical Exhibit List: 4.1 Attachment 1/Technical Exhibit 1 - Performance Requirements 4.2. Attachment 2/Technical Exhibit 2 - Deliverables Schedule See Attachment for Exhibits See Attachment for Solicitation and Contract Terms and Conditions
 
Web Link
FBO.gov Permalink
(https://www.fbo.gov/spg/USA/USAMRAA/DAMD17/W81XWH12R0065/listing.html)
 
Place of Performance
Address: US Army Medical Research Acquisition Activity ATTN: MCMR-AAA, 820 Chandler Street Frederick MD
Zip Code: 21702-5014
 
Record
SN02887894-W 20120920/120919001734-ac9fba501d73a11b226569d7b55eeec5 (fbodaily.com)
 
Source
FedBizOpps Link to This Notice
(may not be valid after Archive Date)

FSG Index  |  This Issue's Index  |  Today's FBO Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers
 Privacy Policy  Jenny in Wanderland!  © 1994-2024, Loren Data Corp.