SOLICITATION NOTICE

45 -- Replace Water Distribution System

Notice Date
3/24/2009
 
Notice Type
Presolicitation
 
NAICS
238220 — Plumbing, Heating, and Air-Conditioning Contractors
 
Contracting Office
Department of Labor, Employment Training Administration, Red Rock Job Corps Center, Route 487 North, Lopez, Pennsylvania, 18628
 
ZIP Code
18628
 
Solicitation Number
WaterSystem2009
 
Archive Date
5/2/2009
 
Point of Contact
Frances J McGraw,, Phone: 570-477-0203, Bob Kocher,, Phone: 570-477-0218
 
E-Mail Address
mcgraw.fran@jobcorps.org, kocher.bob@jobcorps.org
 
Small Business Set-Aside
N/A
 
Description
Design Objectives This project will replace the center’s existing water distribution system, consisting of approximately 4,200 LF of six (6) – inch Transite pipe, plus lesser amounts of smaller diameter pipes. The new system will provide water service to all of the existing and proposed buildings and will include: a.Reconnection of existing building services b.Inclusion of at least six (6) strategically placed isolation valves. These valves will be of new material c.Post indicator valves for fire services, as required. d.Fire hydrant protection for existing and proposed buildings. These will be removed, restored to good working condition and reinstalled on the new system as required. Surplus hydrants will be salvaged and delivered to the center. e.Additional fittings such as blow-off valves, air relief valves, etc., as required by the design. The base material will be PVC to AWWA 900 for the larger lines and PVC to other applicable standards below the range of AWWA 900. Install 8 valves in the six-inch distribution lines. The system will be designed in accordance with the latest version of NFPA 1141, Standard for Fire Protection in Planned Building Groups. Hydrant installation and marking shall conform to the requirement of the local Fire Marshal. The system will be designed to provide a minimum flow of 1,000 gallons per minute at any fire hydrant on the system.
 
Web Link
FedBizOpps Complete View
(https://www.fbo.gov/?s=opportunity&mode=form&id=cfe53900561d6e7856043a899c58a2d9&tab=core&_cview=1)
 
Place of Performance
Address: MTC/Red Rock Job Corps Center, Route 487 North, Lopez, Pennsylvania, 18628, United States
Zip Code: 18628
 
Record
SN01776770-W 20090326/090324220938-cfe53900561d6e7856043a899c58a2d9 (fbodaily.com)
 
Source
FedBizOpps Link to This Notice
(may not be valid after Archive Date)

FSG Index  |  This Issue's Index  |  Today's FBO Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers
 Privacy Policy  Jenny in Wanderland!  © 1994-2024, Loren Data Corp.