MODIFICATION
Z--Z -- Upgrade Chiller - Phase 3
- Notice Date
- 8/16/2006
- Notice Type
- Modification
- Contracting Office
- Attn: Department of Veterans Affairs Maryland Health Care System, 10 North Greene Street, Baltimore, Maryland 21201
- ZIP Code
- 21201
- Solicitation Number
- 512(P)-93
- Response Due
- 8/23/2006
- Archive Date
- 9/22/2006
- Small Business Set-Aside
- 8a Competitive
- Description
- Amendment #1 QUESTION: Feeder to the motor control center. It is currently a 350 MCM feeder on the prints and has been verified in the field. The new work calls for a parallel set of 500 MCM feeders to be run to the 1600 Amp motor control center. ANSWER: Note 15 on Drawings 321-E3 shall read: Provide new set of 4 #350 MCM and 1 #1 ground, type XHHW (match existing) in spare duct. All other terms, conditions, specifications and drawings remain unchanged.
- Place of Performance
- Address: Perry Point, Maryland
- Zip Code: 21902
- Country: United States
- Zip Code: 21902