SOLICITATION NOTICE
N -- ELECTRICAL WORK FOR BUILDING 215, CONTROL ROOM
- Notice Date
- 8/8/2003
- Notice Type
- Solicitation Notice
- Contracting Office
- TACOM - Warren, ATTN: AMSTA-AQ-AMB, E Eleven Mile Road, Warren, MI 48397-5000
- ZIP Code
- 48397-5000
- Solicitation Number
- DAAE08-03-R-A508
- Response Due
- 8/27/2003
- Archive Date
- 10/26/2003
- Point of Contact
- Carol Monsour, 586-574-7095
- E-Mail Address
-
Email your questions to TACOM - Warren
(monsourc@tacom.army.mil)
- Small Business Set-Aside
- Total Small Business
- Description
- NA FURNISH NECESSARY LABOR, MATERIALS AND EQUIPMENT TO INSTALL THE FOLLOWING: 1. REMOVE THE EXISTING TWO LIEBERT POWER CONDITIONERS AND DISPOSE IT OFF DETROIT ARSENAL AS PER ALL PERTINENT REGULATIONS. ALL WIRING AND CONDUITS SHALL BE REMOVED BACK TO SUPPLY ELECTRICAL PANEL. 2. INSTALL A NEW 150 KVA POWER DISTRIBUTION UNIT (PDU), 3-PHASE 480 VOLT INPUT (THREE-WIRE PLUS GROUND), AND 3-PHASE 208 VOLT OUTPUT (FOUR-WIRE PLUS GROUND), SERIES 7200, 72A-8DLX-150K13-AOM2020-A-C OF CONTROLLED POWER COMPANY OR EQUIVALENT). THE PDU SHAL L HAVE A 250 AMP. INPUT BREAKER, AND 2 EA 225 AMP OUTPUT BREAKER. PROVIDE POWER OUTPUT MONITOR WITH TCP/IP INTERFACE CAPAPBILITY. 3. PROVIDE TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS@120KA/PHASE) DEVICES AT THE PDU INPUT. 4. INSTALL THE NEW PDU IN THE MEZZANINE AREA OUTSIDE THE CONTROL ROOM. POWER TO THE PDU SHALL BE OBTAINED FROM EXISTING SPARE CAPACITY IN SERVICE PANEL AT THE MEZZANINIE. ALL CONDUITS SHOULD BE EMT AND SIZED ACCORDING TO NEC REGULATIONS. 5. INSTALL TWO ELECTRICAL PANELS (PDU SUB A, AND PDU SUB B) IN THE CONTROL ROOM, SQUARE D TYPE NQOD30L225CU OR EQUIVALENT, ONE IN THE SOUTHSIDE AND THE OTHER IN THE NORTHSIDE OF THE CONTROL ROOM. EACH PANEL SHALL BE 208/120 VOLT, 225 A. MLO, 3-PHASE 5W (I G BUS). INSTALL ONE 50 AMP 2-POLE BREAKER, TWO 30 AMP 2-POLE BREAKERS, TWO 30 AMP 3-POLE BREAKERS AND FIFTEEN 20 AMP 1-POLE BREAKER IN EACH ELELCTRICAL PANEL. 6. PROVIDE SPECIAL OUTLETS AT LOCATION INDICATED IN THE CONTROL ROOM. 7. FURTHER SCOPE OF WORK WILL BE PROVIDE WITH THE SOLICIATION DAAE08-03-R-A508. MAGNITUDE OF CONSTRUCTION PROJECT IS $25,000.00 - $100,000.00 THIS ACTION WILL BE 100 PERCENT SET-ASIDE FOR SMALL BUSINESS. RELEASE OF THE SOLICIATION IS ANTICIPATED ON 13 AUG 2003. THERE WILL BE A SITE TOUR AT THE U.S. ARMY TACOM ON MONDAY, 18 AUG 2003 AT 9:30. THERE WILL BE ONLY ONE SITE VISIT CONDUCTED. RESERVA TIONS NEED TO BE MADE TO CAROL MONSOUR AT 586-574-7095, EMAIL MONSOURC@TACOM.ARMY.MIL THE SUCCESSFUL OFFEROR MUST BE REGISTERED IN THE DOD CENTRAL CONTRACTOR REGISTRATION (CCR) DATABASE. IT IS THE RESPONSIBILTY OF THE OFFERORS TO CHECK THIS WEBSITE PERIODALLY FOR ANY CHANGES OR AMENDMENTS. WAGE DETERMINATION FOR MACOMB COUNTY, GENERAL DECISION NUMBER MI030082, DATED 13 JUN 2003 APPLIES.
- Place of Performance
- Address: TACOM - Warren ATTN: AMSTA-AQ-AMB, E Eleven Mile Road Warren MI
- Zip Code: 48397-5000
- Country: US
- Zip Code: 48397-5000
- Record
- SN00396310-W 20030810/030808213827 (fbodaily.com)
- Source
-
FedBizOpps.gov Link to This Notice
(may not be valid after Archive Date)
| FSG Index | This Issue's Index | Today's FBO Daily Index Page |